Help in case of faults
10.2 Assignment of error codes
In case of a fault, the error codes will be displayed on the 7 segment display on the base board.
Error code
Description
----
No voltage
U
Voltage below specification
O
Housing internal
temperature too high (>80
°C)
S
Time from end position
to end position too long (>
120s)
Voltage above specification
Heating defective and T =
< 0 °C
e
Error in position detection
P
Invalid position
E
Emergency manual override
active
9
No communication with
accessories
I
Actuator was run in motor
current limit
Further error codes can be found in the corresponding accessory user manuals.
66
"Ready-to-operate"
signal
No
No
No
No
No
No
No
No
No
No
No
Instruction manual
EA response
None
None
Stops
Stops
Stops
Normal
operation
None
Normal
operation
None
None
Stops