Herunterladen Inhalt Inhalt Diese Seite drucken

Installation Precautions; Installation Location; Remote Control Wiring - Panasonic CZ-RTC5 Einbauanleitung

Vorschau ausblenden Andere Handbücher für CZ-RTC5:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 40

Installation Precautions

Installation location

Floor

Remote control wiring

 Wiring diagram
Indoor unit
R1
R2
RC wiring (fi eld supply)
• No polarity
Terminals for RC wiring
 Type of wiring
 Use cables of 0.5 to 1.25 mm
 Total wire length: 500 m or less
(The wire length between indoor units
should be 200 m or less.)
 Number of connectable units
Remote controller: Max. 2
Indoor unit: Max. 8
6
(EN)
5 mm or more
50 mm or
more
1 to 1.5 m
.
2
 Install at the height of 1 to 1.5 m from
the fl oor (Location where average
room temperature can be detected).
 Install vertically against the fl oor.
 When installing more than 1 remote
controller next to each other, keep
distance of 5 mm on the right and left
and 50 mm on top and bottom.
 Avoid the following locations for
installation.
• By the window, etc. exposed to
direct sunlight or direct air
• In the shadow or backside of objects
deviated from the room airfl ow.
• Location where condensation
occurs (The remote controller is not
moisture proof or drip proof.)
• Location near heat source
• Uneven surface
 Keep distance of 1 m or more from
the TV, radio and PC. (Cause of fuzzy
images or noise)
Attention
RC
 Use the fi eld supplied RC wiring
1
with at least 1 mm in thickness of
2
insulation part including the sheath.
Regulations on wire diameters
differ from locally to locally. For
fi eld wiring rules, please refer to
your LOCAL ELECTRICAL CODES
before beginning. You must ensure
that installation complies with
relevant rules and regulations.
 Be careful not to connect cables
to other terminals of indoor
units (e.g. power source wiring
terminal). Malfunction may occur.
 Do not bundle together with the
power source wiring or store in
the same metal tube. Operation
error may occur.
 If noise is induced to the unit
power supply, attach a noise fi lter.

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis