Causes of malfunction
Fault clearance
Checking the switching signal
LEVEL SWITCH 8110 - Tuning fork level switch
7 Maintenance and fault rectification
7.1 Maintenance
When used as directed in normal operation, LEVEL SWITCH
8110 is completely maintenance free.
7.2 Remove interferences
LEVEL SWITCH 8110 offers maximum reliability. Neverthe-
less, faults can occur during operation. These may be caused
by the following, e.g.:
Sensor
l
Process
l
Supply
l
Signal processing
l
The first measure to be taken is to check the output signal. In
many cases, the causes can be determined this way and the
faults rectified.
?
Control lamps off
l
Voltage supply interrupted.
à
Check the voltage supply and the cable connection
à
Exchange the electronics module
?
Signal lamp flashes red
l
There was no load connected when connecting to
power supply
à
Connect the instrument correctly
à
Check if the tuning fork is damage or extremely
corroded
l
Frequency error
à
Adjust the instrument correctly
?
The signal lamp flashes alternately red and green
l
Shortcircuit or overload
à
Check the electrical connection
Maintenance and fault rectification