Herunterladen Diese Seite drucken

Application; External Capacity Control (Ext.) - Siemens CPS 40 Installations- Und Bedienungsanleitung

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Mode of
operation
44/124
Building Technologies
HVAC Products

6.3 Application

PolyCool™ Superheat supports four different types of
application (configuration modes).
Application 1 represents pure superheat control (default). It
has been described in the previous chapter. The other three
applications are the following:

6.3.1 External capacity control (EXT.)

Input X4 can be used to directly change the setpoint of
superheat within the limits specified in the parameter mode
(SMX) by applying a DC 0...10 V / 4...20 mA signal based
on the configuration of external signal direction (SD).
Usually, this signal is delivered by an external controller (i.e.
Synco, Saphir and other third-party.) whose task it is to
maintain the medium temperature at a constant level. The
controller measures the medium temperature, calculates the
manipulated variable and converts it to a DC 0...10 V /
4...20 mA signal.
10 V / 20 mA ≅ min. Q
0 V / 4 mA ≅ max. Q
When SD=1 (see page 36, picture 12)
CPS40
0
(100 %)
0
CE1U3372XX / H 74 319 0555 0 a
22.09.2006

Werbung