Building Technologies
HVAC Products
1

Introduction

This manual contains all the information required to install,
operate and commission PolyCool™ Superheat. All the
required user-specific settings can be made directly on the
device, without the use of additional tools.
2

Functional description

The following functions allow an optimal filling of the
evaporator by using PolyCool™ Superheat:
Control of the superheat
Monitoring of minimum superheat
MOP function (Maximum Operating Pressure)
Monitoring of pressure and temperature sensor
Alarm contact: The monitoring function can,
depending on the wiring, activate an alarm horn or
be integrated into the safety chain of the
compressor.
Service function (manual opening of the valve)
Optionally, it is possible to configure control of the cooling
capacity (refer to chapter 6)
3

System components

PolyCool™ Superheat contains the following components:
Controller: RWR462.10
Electronic injection valve: MVL661...-...
Pressure sensor: QBE9101-P10U with 4...20 mA output
signal
Temperature sensor: QAZ21.682/101, -50...80 °C /
-58...176 °F
The devices above require a supply voltage of AC / DC 24 V.
For AC 24 V, we recommend an isolation transformer with a
minimum of 25 VA.
CPS40
CE1U3372XX / H 74 319 0555 0 a
22.09.2006