Herunterladen Inhalt Inhalt Diese Seite drucken

Conformity With Standards And Directives; Technical Data, Statements - Oeg Rt1 Anleitungen

Raumthermostat
Inhaltsverzeichnis
Verfügbare Sprachen

Verfügbare Sprachen

Technical data
Model: ............................................ RT1
Operation method: ......................... P– controller (ON / OFF)
Power supply:................................. 2 batteries LR03, type AAA
Relay output: .................................. 230 V ~ / 6 (2) A
Consumption: ................................. I= 0,022 mA; P= 0,066 mW
Temperature sensor:...................... Murata NTC (10 kE)
Safety class:................................... IP 30 by SIST EN 60529
Degree of protection:...................... II by EN 60730-1
Housing: ......................................... ABS thermoplastic, white
Dimensions (l × w × h): .................. 72 × 32 × 112 [mm]
Weight: ........................................... 150 g

Conformity with standards and directives

Seltron d.o.o. declares, with full responsibility, that room
thermostat RT1 meets the requirements and rules for the
electrical equipment, designed to use within certain voltage levels
(EC directive for low voltage (LVD) 73/23 EEC, 93/68 EEC) and
requirements and rules for electro-magnetic compatibility (EMC)
(EC directive for electro-magnetic compatibility 89/336 EEC,
92/31 EEC, 93/68 EEC).
Product description:
Room thermostat RT1
Applied standards:
EN 60730-1:1995, EN60730-2-9:1997,
EN 50081-1:1995, EN 50082-1:1995,
EN 55014-1:2001, EN 55014-2:1997.