Herunterladen Inhalt Inhalt Diese Seite drucken

Motor Protection - Helios GigaBox GBW EC-Serie Montage- Und Betriebsvorschrift

Rc-radialventilatoren
Vorschau ausblenden Andere Handbücher für GigaBox GBW EC-Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Montage- und Betriebsvorschrift
WARNING
WARNING
Centrifugal fans – GigaBox GBW EC.. / GBD EC..
– with universal control system EUR EC
For stepless control or adjustment of single- and 3-phase EC-fans with an input control signal of 0 - 10 V DC. Con-
nection excamples of the basic scheme are mentioned further below.
Basic scheme:
Example 1: Temperature control with additional function
and differental temperture control
fig.2
The use of other brands, especially other electronic devices, can lead to malfunctioning and even destruc-
tion of controller and/or fan. Controllers which have not been cleared by Helios are not liable for warranty and
guarantee claims.
Control of several EC-fans with a potentiometer
In order to control several EC-fans via the setpoint input "0-10V", the 10VDC -voltage source must provide the
sum of all setpoint input burden currents.
Parallel connection of +10VDC supply of serveral EC-fans is not permitted!
Depending on the type several EC-fans can be controlled with the 10VDC supply from a fan with a potentiometer
(PU/A). For this see the technical data of the control inputs and the wiring diagram SS-1035.
If the power of the EC-supply is not sufficient a customer-supplied sufficient external 10VDC can be used (gavani-
cally separeted from the mains).
Alternatively the Helios module „ EUR EC" can be used for varied control duties.

1.17 Motor protection

All Gigabox units are equipped with energy-saving, maintenance-free EC-external rotor motors ( protected to IP 54,
radio suppressed, with ball bearing) with highest efficiency. Suitable for continous operation S1. Insulation class F. Fur-
thermore the motors are equipped with an integrated electronic protective function. The following functions are super-
vised:
– Locked rotor
If the rotor is locked, the motor tries a restart after 5 s, with a second failed attempt the motor is switched off. The error
is indicated over the fail safe relay after 10 s. The restart of the fan is possible only over switching the mains voltage off
for min. 30 s.
– Overtemperature electronics
If the maximum temperature is reached in electronics, electronics reduces the speed automatically.
– Overtemperture motor
If the maximum temperture in the motor is reached, the thermal contact trips and the motor is swiched off. The error is
displayed over the fail safe relais after 10 seconds. The restart of the fan is possible only over switching the mains vol-
tage off for min. 30 s.
– Overcurrent error
Due to a blocking of the impeller during the operation as well as a short-circuit in the motor, an overcurrent error may
occur. The motor is switched off. The error is displayed over the fail safe relais after 10 seconds.The restart of the fan is
possible only over switching the mains voltage off for min. 30 s.
– Mains undervoltage
If the mains input voltage falls 20 % under the mains voltage specified in each case, the motor is switched off. The error
is displayed over the fail safe relais after 10 seconds. The restart of the fan takes place automatically with return of the
normal mains voltage.
– Mains overvoltage
If the mains input voltage rises 10 % over the mains voltage in each case, the motor is swiched off. The error is dis-
played over the fail safe relais after 10 seconds. The restart of the fan takes place automatically with return of the nor-
mal mains voltage.
– Overspeed
With exceeding of the maximally permissible fan speed the motor is switched off. The error is displayed over the fail
safe relais after 10 seconds.The restart of the fan is possible only over switching the mains voltage off for min. 30 s.
Example 2: Differential pressure control and air velocity
control
fig.3
3
UK

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis