INSTALLATION

Fig.1 - DIMENSIONS (mm):
85
IMPORTANT: - The installation of this device must be carried out by specialized technicians.
- Caution, do not connect the battery charger:
1
1
- Do not carry out any maintenance when the battery charger is connected to the
230Va.c. power supply net.
- In case of battery charger's misuse, the guarantee falls off and the manufacturer
declines all responsibility for damages to people and things.

BATTERY CHARGER

- Install the battery charger in an appropriate housing, dry and ventilated; maximum efficiency can be
obtained when the battery charger is installed in vertical position (see figure 2), keeping the front side
at minimum distance of 300 mm and the bottom and top side at a minimum distance of 100 mm from
the housing sides.
- Do not cover air intakes.
- To guarantee a proper change of air the installation of two air intakes (one placed on the top and one
on the bottom, see figure 2) ensuring a working temperature inside the housing not exceeding 50 °C.
- Make sure that the 230Va.c. safety switch can be easily reached.
- The connection to power supply mains shall be made in accordance with national installation rules.
- Before disconnecting the battery charger from 230Va.c. power supply, turn the safety switch off.
- The installation requires the fixing of no. 4 pins that can be easily placed on the 4 sides.
- The battery charger can be installed together with CBE 12V and 230V distribution panels, using the
appropriate modular joints.
CABLES
- Use cables with appropriate section, minimum cross section area 4 mm².
- Protect cables from any possible damage.
BATTERY
- Lead-acid batteries shall be positioned in a well ventilated place.
- Use only 12Vd.c. rechargeable lead batteries (capacity >40Ah).
Warning:
- Do not use "not rechargeable" batteries.
- Exhausted batteries shall be disposed in accordance with existing environmental protection
regulations.
157
110
140
when a generator set with non stabilised output voltage is employed
with power mains voltage exceeding the rated value (230Va.c. ±10%)
Fig.2 - VERTICAL INSTALLATION