hoW To DisManTlE sysTEM 4000
First, remember to demount the connectors with hazardous voltages.
When front lED lights red / display shows ao.ER
PR 4116 is designed as a SIL 2 device with a high safety level. Therefore, a
continuous measurement of the outgoing current is carried out on a 4...20
mA output signal. If the current is 0, an error mode switches on the red front
LED and disables the relays. This function is not a default option but must be
actively selected in the menu. The error mode can only be reset by switching
off and then switching on the supply voltage to the device.
38
Picture 1:
Detach the device from the DIN rail
by lifting the bottom lock.