Transducer for measuring frequency SINEAX F 534
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then ... ................................................. 9
2. Brief description ......................................................... 9
3. Technical data ............................................................ 9
4. Mounting ................................................................... 10
5. Electrical connections ............................................... 10
6. Commissioning and maintenance ............................ 11
7. Releasing the transducer .......................................... 11
8. Dimensional drawing ................................................ 11
9. Instruments admissions ............................................ 11

1. Read first and then ...

The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully and the safety warnings given
in the various Sections
4. Mounting
5. Electrical connections
are observed.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.

2. Brief description

The transducer SINEAX F 534 is intended for frequency
measurement. The instrument change the measured value
into a proportional load-independent DC current or DC
voltage.

3. Technical data

Measuring input
≥ 10 Hz, f
Measuring range:
f
a
f
/(f
a
e
f
: Measuring range start frequence
a
f
: Measuring range end frequence
e
Nominal frequency:
See type label
Nominal input
voltage:
10 - 230 or > 230 - 690 V
≤ 1500 Hz
e
-f
) < 50
a
Measuring output
DC current:
0(0.2) - 1 to 0(4) - 20 mA
± 1 to ± 20 mA
Load voltage:
- 12 V / 15 V
max. [kΩ] ≤
External resistance:
R
ext
resp. ≤
I
= Full scale output
AN
DC voltage:
0(0.2) - 1 to 0(2) - 10 V
± 1 to ± 10 V
Load capacity:
Max. 4 mA
Power supply
AC/DC power pack (DC or 40 - 400 Hz)
Rated voltage
85 - 230 V DC / AC
24 - 60 V DC / AC
≤ 2.5 W resp. ≤ 3.5 VA
Power consumption:
Options
Connected to the low
tension terminal side:
24 V AC or 24 - 60 V DC, see Fig. 4
Power supply from
measuring input
≥ 24 - 60 V AC or 85 - 230 V AC,
(self powered):
see Fig. 3
Please note the max. and min. measuring input voltage!
Type label
Input voltage
inscription
range
= internal power
supply range
Self powered
by 1/2
24 - 60 V AC
(int. 24-60 V)
Self powered
by 1/2
85 - 230 V AC
(int. 85-230 V)
Accuracy (acc. to IEC 688)
Reference value:
Output span
Basic accuracy:
Class 0.2
Safety
Pollution degree:
2
Installation category:
III
Environmental conditions
Operating temperature: - 10 to + 55 °C
- 40 to + 70 °C
Storage temperature:
Relative humidity of
≤ 75%
annual mean:
15 V
I
[mA]
AN
- 12 V
- I
[mA]
AN
Tolerance
DC - 15 to + 33%
AC ± 15%
Tolerance Power
supply
connec-
tion
Internal
± 15%
measuring
input
9