4. Mounting

The SINEAX F 534 can be mounted on a top-hat rail.
Note "Environmental conditions" in Section
"3. Technical data" when deteriming the place
of installation!
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 1).
Fig. 1. Mounting on top-hat rail 35 × 15 or 35 × 7.5 mm.

5. Electrical connections

Connect the leads acc. to the instructions on nameplate.
Make sure that all cables are not live when
making the connections!
Impending danger by high input voltage
or high power supply voltage!
Note that, ...
... the data required to carry out the prescribed
measurement must correspond to those
marked on the nameplate of the SINEAX F 534
(
measuring input,
and
power supply, see Fig. 5)!
... the resistance in the output circuit may not
overrange the current output value
max. [kΩ] ≤
R
ext
(I
= current output value)
AN
and not underrange the voltage output value
min. [kΩ] ≥
R
ext
(U
= voltage output value)
AN
... the measurement output cables should be
twisted pairs and run as far as possible away
from heavy current cables!
In all other respects, observe all local regulations
when selecting the type of electrical cable and
installing them!
10
measuring output
15 V
– 12 V
resp. ≤
I
[mA]
– I
[mA]
AN
AN
U
[V]
AN
4 mA
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
U
Fig. 2. Power supply
connected to terminals
8 and 9.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
U
Fig. 4. Power supply
connected to the low tension
terminal side 12 and 13.
Output
Output signal
10
11
12 13
+
4-20mA
SINEAX F 534
Ord: 000/00F534/010/1
49.5 - 50.5 Hz
230 - 690 V
U
1
2
3
4 5
6
Input
Power
Measuring range
supply
Measured quantity
Fig. 5. Declaration to type label.
– +
10
11
12 13
1
2
3
4 5
6
7
8
9
U
Fig. 3. Power supply internal
from measuring input, without
separated power supply
connected.
= Measuring
input
= Measuring
output
= Power supply
0,2
Test markes
85-230V DC/AC
Works No.
40-400Hz 3.5VA
+
7
8
9

Werbung