de | 2. Environmental protection
Intended use
  
Air quality controller for controlling fresh
air supply, dependant on the room air
quality.
Only for use in living areas.
Predictable misuse
The unit should not be used:
Close to flammable materials, liquids or
gasses.
In areas subject to explosion hazards.
For safety applications.

2. Environmental protection

The unit and the packaging contain parts
that can be recycled, and should not end
up in the domestic waste. Unpack the unit.
Please dispose of the packaging material
in an environmentally-friendly way in
compliance with the regulations valid in the
country where you are.

3. Product information

Product description
Air quality controller sensor for controlling
the ventilation unit depending on the air
quality. The integrated air quality sensor is
used for measuring the concentration of
various gases and odours (e.g. carbon
monoxide, methane, hydrogen, alcohol,
tobacco smoke).
The sensor is programmed exclusively for
connection to the WRG units (WS 170,
WR 300, WR 400 and WR 600) and has a
0...10 V output.
After applying power, the warm-up time is
15 minutes.
 
6
Technical data
VOC sensor
Metal oxide sensor with
element
Measurement
range
Output
Power supply
Type of voltage
Current input
Connecting
terminal
Degree of
protection
Weight
Measurements
(L/W/H)

4. Mounting instructions

When installing the sensor module it must
be ensured that there is unimpeded air
circulation so that the measurement data
can be recorded in as timely and as "true"
as possible.
Recommendations
At least 50 cm distance from adjacent
walls.
Not in niches on external walls, nor
behind curtains.
Not on walls that have a chimney behind
them, for example.
Permitted application area: Interior
rooms, 0...50°C, 5...95% rel. humidity.
(without condensation)
automatic calibration
800-1200 ppm / CO²
equivalent
0 ... 10 V
12-25 VAC or 12-
35 VDC
Alternating current/
Direct current
Max. 14 mA
Plug with screw
terminals for
0.25...1.5 mm²
IP 30
58 g
72 x 72 x 27 mm