Bender CP700 Kurzanleitung Seite 4

Vorschau ausblenden Andere Handbücher für CP700:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CP700
5. Commissioning of the device
1.
Switch the supply voltage on. - The "Settings" > "Interface"
menu will appear on the touch screen. Click on "Login" to carry
out the settings (logged in).
2.
Set the IP address.
If the connected computer network contains a DHCP server,
activate the "DHCP" button. The IP address is automatically
obtained and displayed.
If the computer network does not provide a DHCP server, the IP
address, network mask (SN) and standard gateway are to be set
as specified by the EDP administrator.
A fixed IP address was assigned to the device. Therefore, acti-
vate the "DHCP" button.
3.
Set the BMS bus address for the CP700.
4.
Modbus/RTU: Set the baud rate and parity.
5.
Set the display timeout. If no entry is made via the touchscreen
of the CP700 for a predefined time (e.g. five minutes), the
screen is blanked.
6.
Confirm the changed settings with "OK". Click on "Logout"
when no settings are to be changed.
7. Using the web user interface
System requirements
Microsoft Silverlight (version 5.0 or higher) must be installed.
JavaScript should be activated; e.g. necessary for report and
software update.
The Pop-up blocker should be deactivated for the IP address.
Otherwise, access to the manual, the software updates and the
network settings could be hampered.
All rights reserved.
Reprinting and duplicating
only with permission of the publisher.
Subject to change!
© Bender GmbH & Co. KG
Bender GmbH & Co. KG
Londorfer Str. 65 • 35305 Grünberg • Germany
Postfach 1161 • 35301 Grünberg • Germany
EN-2
6. Operation via touch screen
The main menu
4
5
1
"Bus overview" button shows a list of the bus devices for
selection, querying and parameterisation.
2
"Alarm" button shows an overview about pending
alarms.
3
The "Settings" button allows the setting of the interface
and the operation language of the device.
4
"Back" button. - One operating step back.
5
"
6
Device type or an individually entered text in the web
user interface.
7
Date and time display.
8
Display "Logged in". Settings in the "Interface" menu can
only be carried out after "Login".
9
The same function as "2", accessible from each sub-
menu.
Getting started
1.
Start the Internet browser
2.
Read the IP address from the "Settings" > "Interface" menu and
enter it in the Internet browser.
3.
Select the user language for the web user interface. Click on
the language you want to use resp. click the appropriate flag.
4.
Click on "Bus overview" to get a graphic representation of all
BMS bus devices.
5.
Select "Tools" > "Manual" to open the operating manual.
Tel.: +49 6401 807-0
Fax: +49 6401 807-259
6
1
2
" button. - Return to the main menu.
D0000500QDEEN
E-Mail: info@bender-de.com
Web: http://www.bender-de.com
CP700_D00005_00_Q_DEEN/05.2013
7
8
9
3