Quick reference guide "Installation and connection"
CP700
Condition monitor for Bender BMS devices and universal measuring devices
This quick reference guide does not replace the operating manual. The operating manual can be found on the web user interface ("Tools" > "Manual")
or in the download area of our homepage. Make sure that the personnel has read this manual and understood all instructions relating to safety.
1. Safety instructions
Danger: Risk of fatal injury from electric shock
Parts of the system are live. During installation and connection:
Do not touch parts of the system.
Disconnect the system from the power supply and protect the
system against accidental switch-on.
Warning: Risk of destruction if mains voltage incorrect
Refer to the nameplate for the permissible mains voltage.
2. Scope of delivery
You will receive:
• the CP700
• the operating instructions are available as PDF file in the
device memory, via the web user interface "Tools" > "Manual"
• this quick reference guide
• a pluggable screw terminal for the power supply
• two RS-485 cables for connection to the BMS bus and the
Modbus/RTU, 2 m
• two terminating resistors each for BMS bus and Modbus/RTU
• four mounting brackets
4. Connection of the device
10
5
4
Connection
1.
Plug-in the RJ45 cable to the PC or LAN (9)
2.
Connect the RS-485 cable for connection to the BMS bus (3)
and to the Modbus/RTU (1). Switch resp. connect the associ-
ated terminating resistors.
3.
Connect the DC 24 V power supply, the functional earth (6)
and earthing connection (7).
CP700_D00005_00_Q_DEEN/05.2013
9
8
7
6
3
2
1
Warning: Malfunction due to double address assignment
Assigning addresses that are already used by existing devices in the
BMS or TCP/IP networks concerned may cause serious malfunctions.
Note: Do not remove the CompactFlash card
In order to ensure the device properties, the CompactFlash card must
not be removed!
3. Installing the device
The CP700 can be installed into control panels and cabinet doors.
Material thickness min./max. = 2 mm/6 mm
1.
Make an installation cut-out of 199 mm x 143 mm and deburr
the surface. The surface of the cut-out must be flat and
smooth. Irregularities in the surface may result in damage to
the display.
2.
Insert the mounting brackets into the CP700 and slide them
down (see orange markings in the picture below).
3.
Fasten the screws of the mounting brackets securely (tighten-
ing torque approx. 0.5 Nm).
1
Interface Modbus/RTU
2
Switch terminating resistor/bus bias voltage for Mod-
bus/RTU interface
3
BMS bus (Bender measuring device interface)
Note: Insert the plug of the BMS connecting cable
into the CP700, otherwise the CP700 will not be dis-
played on the web user interface
4
Switch terminating resistor/bus bias voltage for BMS
bus
5
USB interface, is not used
6
Connection of the DC 24 V voltage supply and the
functional earth
7
Earthing connection
8
USB interfaces, are not used
9
Ethernet 10/100/1000, RJ45 socket for connection to
PC resp. the local network (hub, switch, router)
10
RS-232 interface, is not used
EN-1