 Picture 14
symbol
button
SCROLL
UP
DOWN
POWER-UP
After power-up the display will show the installed software
version for a period of 5 seconds.
POWER FAILURE
In the event of a power failure, the program will remain
stored in the NOVRAM® during an undefined period, while an
incorporated SuperCap will maintain the correct time of day
during a period of several hours; consequently, in case of
prolonged power failure, the time of day might not be
maintained; if this happens, the time of day will be reset to
8:00 when the power supply is re-established, while the
indication will flash, indicating that the time of day needs to
be set.
When the power failure occurs during the execution of an
automatic regeneration, the control valve will remain in its
last position; when the power supply is re-established, the
control valve will return to the service position, stay there for
60 sec. and restart a complete regeneration from the
beginning.
TIMER FAILURE
In the event of a timer failure, the display will show the
message:
Service Required
If powering off/on the appliance doesn't solve this problem,
professional service is required.
MAINTENANCE REMINDER
Once the maintenance interval is reached, the display will
intermittently show the message:
Maintenance Now
While the appliance will continue to operate normally, it is
recommended to have preventive maintenance performed
by a professional.
SERVICE MODE
In service mode the display shows:
Simplex, Duplex Parallel: the time of day and the
remaining capacity:
8:01
1000L -

ELECTRONIC CONTROL PANEL

function
to advance to the next
parameter
to increase the value of the
parameter
to decrease the value of the
parameter
Duplex Alternating: the systems status (Service or
Standby) and the remaining capacity:
Srvc
Stdby
REGENERATION MODE
In regeneration mode the display shows:
Simplex,
Duplex
regeneration time and remaining cycle time:
Rgn:123 CycY:456
Duplex Alternating: the total remaining regeneration
time and remaining cycle time:
Rgn:123 CycY:456
When the regeneration is finished, the system remains in
Standby, until the other system starts a regeneration:
Stdby
The appliance can be reset to service mode at any time by
pressing the scroll
through the regeneration cycles.
CHECKING THE FLOW METER
In case of water usage, the remaining capacity counter in the
service display will count back. This way the correct
functioning of the water meter can be verified.
MANUAL REGENERATION
It is possible to manually initiate an immediate regeneration
or a delayed regeneration (at the preprogrammed time of
regeneration).
1. Press the scroll
Regen in 10 sec
If the control panel is left in this position, the
countdown timer will countdown to 0 sec and start an
immediate regeneration.
To cancel this mode, press the scroll
the countdown timer has reached 0 sec; the display
will show:
Regen @
If the control panel is left in this position, a delayed
regeneration will be started at the indicated
preprogrammed time of regeneration.
To cancel this mode, press the scroll
control panel will return to the service mode.
Page 11
1000L -
1000L -
Parallel:
the
total
1000L -
button, as such manually advancing it
button; the display will show:
button before
2:00
button; the
EN - English
remaining