20. Troubleshooting
NO
NO
NO
NO
END
EN-18
Appliance does not heat
Red indicator
flashes
Air trapped in heat
exchanger
Fault is still present?
YES
W ater temperature too
low
Fault is still present?
YES
Insufficient water flow rate
through device
Fault is still present?
YES
Dirt on heat exchanger
Fault is still present?
YES
Contact your installer or
the Service hotlinie
SRX_gb · 01/15/B
Disconnect device from power supply, remove
casing and bleed heat exchanger. For position
of bleeder screw, see figure 5
Set flow temperature higher on heating system
Adjust flow rate (hydraulic balance). To do this,
close thermostat valves on the other heaters.
Clean heat exchanger, see "Maintenance"
section