Wiring
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The instalation must be protected by a circuit breaker and a Residual Current Device 30 mA -
Class A, installed in the switchboard. Systems that automatically reset the Residual Current Device
are prohibited. An undervoltage remote tripping auxiliary associated with the circuit breaker can be
added as an optional protection.
Those electrical protections and the supply cable must be used only for the charging station and
must be compliant with the electrical installation standard in force.
Do not commission nor use the charging station if the measured earthing resistance is higher than
the threshold specified by the local regulation in force.
Failure to follow these instructions will result in death or serious injury.
NOTICE
DAMAGE TO CHARGING STATION
Do not touch the electronic boards, use Electrostatic Discharge Devices before working inside the
charging station..
A Surge Protection Device should be connected close to the charging station according to the
Keraunic level of the installation area (*). The Surge Protection Device should be connected
between the circuit breaker and the charging station, close to the charging station.
Failure to follow these instructions can result in equipment damage.