Herunterladen Inhalt Inhalt Diese Seite drucken

Storage Mode: Less Corrosion Of The Positive Plates; Reconditioning; Lithium-Ion (Lifepo₄) Batteries - Victron energy Blue Power Charger IP22 12/15 Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 41
Adaptive Battery Management limits corrosion by reducing
absorption time when possible, that is: when charging a battery
that is already (nearly) fully charged.

2.6 Storage mode: less corrosion of the positive plates

Even the lower float charge voltage that follows the absorption
period will cause grid corrosion. It is therefore essential to reduce
the charge voltage even further when the battery remains
connected to the charger during more than 48 hours.

2.7 Reconditioning

A lead-acid battery that has been insufficiently charged or has
been left discharged during days or weeks will deteriorate due to
sulfation¹. If caught in time, sulfation can sometimes be partially
reversed by charging the battery with low current up to a higher
voltage.
Remarks:
a)
Reconditioning should be applied only occasionally to flat plate VRLA
(gel and AGM) batteries because the resulting gassing will dry out the
electrolyte.
b)
Cylindrical cell VRLA batteries build more internal pressure before
gassing and will therefore lose less water when subjected to
reconditioning. Some manufacturers of cylindrical cell batteries
therefore recommend the reconditioning setting in case of cyclic
application.
c)
Reconditioning can be applied to flooded batteries to 'equalise' the
cells and to prevent acid stratification.
d)
Some battery charger manufactures recommend pulse charging to
reverse sulfation. However, most battery experts agree that there is
no conclusive proof that pulse charging works any better than low
current / high voltage charging. This is confirmed by our own tests.
2.8 Lithium-ion (LiFePO₄) batteries
NEVER attempt to charge a Li-ion battery when its temperature is
below 0°C.
¹ For more information about batteries, please refer to our book 'Energy
Unlimited' (downloadable from www.victronenergy.com),or
http://batteryuniversity.com/learn/article/sulfation_and_how_to_prevent_it
² For more information about Li-ion batteries please see
http://www.victronenergy.com/batteries/lithium-battery-12,8v/
4

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Blue power charger ip22 12/20Blue power charger ip22 24/12Blue power charger ip22 24/08Blue power charger ip22 12/30Blue power charger ip22 24/15

Inhaltsverzeichnis