Herunterladen Diese Seite drucken

Generex CS121 Serie Benutzerhandbuch Seite 72

Werbung

149
U
3 / 4 xid645 Bits 16-31
150
U
3 / 4 xid645 Bits 32-47
151
U
3 / 4 xid645 Bits 48-63
Section OEM
MASTERGUARD
139
U
3 / 4 PXWARN
141
U
3 / 4 FAULT CODE 1
142
U
3 / 4 FAULT CODE 2
143
U
3 / 4 FAULT CODE 3
144
U
3 / 4 FAULT CODE 4
145
U
3 / 4 BADBATTBLOCK 1
146
U
3 / 4 BADBATTBLOCK 1
147
U
3 / 4 BADBATTBLOCK 1
148
U
3 / 4 BADBATTBLOCK 1
149
U
3 / 4 BADBATTBLOCK 1
150
U
3 / 4 BADBATTBLOCK 1
Section OEM
RITTAL
Digital Input Status(DI)
0
bit
2
Bypass working
1
bit
2
Bypass Interruption
2
bit
2
Rectifier Failure
3
bit
2
Inverter Failure
4
bit
2
Over Temperature
5
bit
2
Over Load
6
bit
2
0
7
bit
2
Battery Voltage too Low
8
bit
2
Fuse broken
9
bit
2
Battery discharging
10
bit
2
0
11~3
bit
2
For future expansion
0
After
bit
2
Venders own definition
31
Analog Measurement point(AI)
00
word 4
R phase input voltage
01
word 4
S phase input voltage
02
word 4
T phase input voltage
03
word 4
R phase input current
04
word 4
S phase input current
05
word 4
T phase input current
06
word 4
Input frequency
07
word 4
R phase output voltage
08
word 4
S phase output voltage
09
word 4
T phase output voltage
10
word 4
R phase out current
11
word 4
S phase output current
12
word 4
T phase output current
72
Alarmbit, for details please
contact NEWAVE
Alarmbit, for details please
contact NEWAVE
Alarmbit, for details please
contact NEWAVE
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Normal, Status 1: Alert
Status 0: Floating charge
Status 1: Instant charging
0.1 Volt
0.1 Volt
0.1 Volt
0.1A
0.1A
0.1A
0.1Hz
0.1 Volt
0.1 Volt
0.1 Volt
0.1A
0.1A
0.1A
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
2

Quicklinks ausblenden: