Herunterladen Inhalt Inhalt Diese Seite drucken

SCYLAR INT8 Installationsanleitung Seite 29

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English
6.5 Combined function module
The combined module is equipped with 2 inputs and 1 output.
Pulse input is specified as stated at 6.3.
Pulse output is specified as stated at 6.4 but not electrically isolated.
6.6 Function module analogue output
The module contains connections for 2 passive analogue outputs,
which can be programmed individual using the IZAR@SET- Soft-
ware.
The outputs are marked „1" and „2" with corresponding polarity
„+" and „-" on the terminal strip.
· Passive, external supply: 10 ... 30V DC
· Current loop 4 ... 20mA
with 4mA = 0 value; 20mA = programmed maximum value
· Overload up to 20,5mA, excess causes error current
· Errors are shown with 3,5mA or 22,6mA (programmable)
· Output values: power, flow, temperature

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis