Start-Up
When all mounting and connection work has been
completed, the functioning of the unit is to be tested.
The following minimum tests should be carried out:
- Insulation test with a voltage of at least 500 V.
- The insulation resistance must be at least 0.5 M
- Measure the power consumption of the device. If
necessary, cold resistance measurement may be carried
out.
Initial heating of units by a specialist is not necessary.
Reassembly
If devices which were already installed and operated are
dismantled and reassembled in another place, they, too,
must be started-up according to the above instructions after
installation. During installation please ensure that the
thermal insulation is not damaged. Damaged parts of the
thermal insulation must be replaced.
The initial charging after reassembly starting with the device
in cold state (room temperature) up to the switching off of the
charge controller must be monitored by a technician.
Measure the electrical energy (kWh) stored. It must not
exceed 125% of the rated charging stated on the power
rating plate.

Technical Device Information

Designation
Brick bundles
VFMi 20C
4 x 25
VFMi 30C
6 x 25
VFMi 40C
8 x 25
VFMi 50C
10 x 25
VFMi 60C
12 x 25
VFMi 70C
14 x 25
*for max 6 h of charging
.
Heating
Nominal
element set
power
HFi 212
1250 W
HFi 216
1600 W
HFi 220
2000 W
HFi 227*
2700 W*
HFi 318
1850 W
HFi 324
2400 W
HFi 330
3000 W
HFi 340*
4000 W*
HFi 425
2500 W
HFi 432
3200 W
HFi 440
4000 W
HFi 452*
5200 W*
HFi 540
4000 W
HFi 550
5000 W
HFi 564*
6400 W*
HFi 648
4800 W
HFi 660
6000 W
HFi 676*
7600 W*
HFi 756
5600 W
HFi 770
7000 W
HFi 790*
9000 W*
Start-Up, Technical Device Information
Repair Notice
Electric storage heaters may only be repaired by qualified
personnel. Repairs which are improperly carried out can
endanger the safety of the user.
The devices have a high-grade thermal insulation. Only
remove the core room cover with integrated thermal
insulation when replcaing the heating elements. All other
electrical components can be accessed by removing the side
panels.
Resetting the Temperature Limiter
Note on Disposal
Do not dispose of the unit with general household
waste. The device must be taken to a local waste
disposal plant.
Nominal
Nominal
voltage
charging
3/NPE
16 kWh
400V 50Hz
3/NPE
400V 50Hz
24 kWh
3/NPE
400V 50Hz
32 kWh
3/NPE
400V 50Hz
40 kWh
3/NPE
400V 50Hz
48 kWh
3/NPE
400V 50Hz
56 kWh
Weight
Transport
Dimensions
weight
W x H x D
626 x 672 x 250
98 kg
34 kg
776 x 672 x 250
137 kg
40 kg
926 x 672 x 250
176 kg
46 kg
1076 x 672 x 250
215 kg
52 kg
1226 x 672 x 250
254 kg
58 kg
1376 x 672 x 250
293 kg
64 kg
mm
mm
mm
mm
mm
mm
19