Wind-/Rain-control unit WRZ 40M-4G
6.0
Electrical connection
6.1
Connection mains 230 V AC
Attention! Before working on the installation, the mains voltage is all poles unlock and secure it against
inadvertent power-cons.
Caution! From incorrect work on live electrical components can lead to electric shock!
The electrical connection must be performed by qualified electricians.
mains supply
230 V AC
6.2
Connection wind/rain detector WRM/2 24V
1. WRM/2 24V
WRZ 40M-4G
1. WRM/2 24V
30
L = Phase
N = Neutral conductor
= safty earth conductorr (PE)
2. WRM/2 24V
2. WRM/2 24V
terminal designation
in the WRM/2 24V
1.
Powersupply +24 V DC
2.
Powersupply -24 V DC
3.
Relay contact (working
contact)
4.
NC-contact (normaly closed)
5.
NO-contact (Normaly Open) or
wind sensor signal
6.
Wind sensor signal
Wind sensor
11
12 13
14 15
DIP switch and Jumper
setting in the WRM/2 24V
DIP switch
Jumper
Jumper 1+4
to display the
wind speed