Troubleshooting Procedure - SLAT SON 24V 12A MS150 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für SON 24V 12A MS150:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

The indicator light are not illuminated
Check the mains voltage (between 195Vac and 265Vac)
Check the primary fuse F1 on the power and control board
Check that the flat ribbon cable is correctly connected
The output indicator light is yellow
Check the output fuses F1 to F6
Check the auxiliary fuses F1 to F3
The battery indicator light is yellow
Check that the nominal battery voltage is ok with the sytem voltage
Check the polarity connections of each battery and on the rack battery connector
Check the battery connections and the battery fuse connections
Check the voltage of each battery block (>1,9V / >5,7V / >10,8V)
Check that the battery is approuved (see Pr 1.2.5)
If the mains is present, check that the output current is <12A
The internal battery resistor may be too high: replace the battery
The mains indicator light is yellow
Check the mains voltage (between 195Vac and 265Vac)
Check the primary fuse F1 on the power and control board
Check that cooling of the rack is sufficient and that the ambient temperature is < 45° C
For additional technical assistance, contact the SLAT hotline
or contact SLAT After-Sales Service to obtain an RMA (Return Material Authorisation) number.

8 Troubleshooting procedure

+ 33 (0) 4 78 66 63 70
For return requests, visit our website
http://www.slat.fr/formulaireRMA.php
Returns are not accepted without an RMA number.