Herunterladen Inhalt Inhalt Diese Seite drucken

General Information; Environmental Specifications; Electrical Input And Output Specifications; Network Input - SLAT SON 24V 12A MS150 Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für SON 24V 12A MS150:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1.1

Environmental specifications

Operating temperature: -5 ° C to +45 ° C at 12 A.
Altitude : over 2000m, the max operating temperature decreases of 5° C every 1000 m.
Cooling operates transversally.
Storage temperature: -25 to +85 ° C.
Operating relative humidity: 20 to 95 % without condensation,
Storage relative humidity: 100 to 95 %.
1.2

Electrical input and output specifications

1.2.1

Network input

single-phase voltage: 195 V to 264 V.
-
frequency: 47 to 63 Hz.
-
power consumption at full load: 380 W (PLN-24CH12) or 760 W (PRS-48CH12).
-
maximum primary current @ 195 V: 2 A (SON 24V 12A MS150 RACK) or 4A (SON 48V 12A
-
MS150 RACK).
class I.
-
neutral and earthing systems: TT, TN, IT.
-
two pole circuit breaker (D curve) to be provided upstream.
-
1.2.2

Output

Rated voltage: 24 V (SON 24V 12A MS150 RACK) or 48V (SON 48V 12A MS150 RACK).
-
Floating voltage set at half-load and at 25 ° C: 27. 2 V
-
6 main outputs with a current of 40A maximum per output (protection see chapter 7)
-
3 auxiliary outputs with a current of 5A maximum per output. (protection see chapter 7)
-
the maximum total current of the 9 outputs is 150A.
-
the power supply can operate without load current: Imin = 0 A.
-
Rated output current of rectifier : 12A
-

1 General information

28
or 54.4V
±0.5 %
+/-0.5%.

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis