3. Loft installation
The water softener should be installed within a con-
tainer of not less than 100 litre capacity, to which
there should be connected an overfl ow pipe of not
less than 20mm diameter. The overfl ow should be
connected at the bottom of the container and not
less than 15mm below the height of any electrical
components mounted on the water softener. It is
recommended that an anti vacuum valve be fi tted
to the inlet pipework supplying the water softener.
4. Plumbing systems
There are several types of plumbing systems in
common use:
For 15mm pipework (e.g.Static Head systems)
The water softener can be supplied optionally
with a high fl ow installation kit and fl exible high
fl ow hoses suitable for 22mm pipework, for 15mm
pipework use the reducing bushes supplied with
the kit, (see diagram on page 11).
10
OPM - Cillit Access 10-25 vOrange - EN, DEv4.indd 10-11
5. Backfl ow prevention device
When fi tted to the supply feeding a single dwelling,
a check valve complying with national regulations
must be fi tted on the cold water feed prior to the
installation. All other types of installation require the
fi tting of a double check valve.
6. Drinking water
Your water softener installation must include at
least one drinking water tap that is not fed by the
water softener.
In case of low sodium diet follow the local
"department of health's" advice concerning the use
of softened water for drinking.
Note: Water that is used for mixing powdered milk
for babies must only be taken from an unsoftened
mains tap as some powdered milks and softened
water both contain sodium for which young babies
have a limited tolerance.
7. Only original spare parts and accessories autho-
rized by the manufacturer guarantee operational
safety. Using non-authorized parts may void any
liability on the part of the manufacturer in case of
consequential damage.

3.4 Installation Layout

To rising
main
Outlet from
softener
N.
Key to the diagram:
A. Non return valve
B. Pressure reducing valve (where required)
C. Inlet valve ¾"
D. Bypass valve
E. Outlet valve ¾"
G. Brine storage cabinet
Rising Main
H. Fixing clip
Valve Head
M.
I. Waste
water
hose
C. Inlet
L.
E. Outlet
O.
Overfl ow *
20 mm
Water softener
P.
K. Overfl ow fl exible hose
*
J. Drainage (
Existing or new "Trapped" stand pipe or to external drainage)
Observe
a minimum distance to the ceiling (N) of 0.5 m.
Inlet from
mains
Inlet to
softener
Key to the diagram:
H. Fixing clip
I. Waste water hose
J. Drainage
K. Flexible hose, Overfl ow
L. Control valve (green)
M. Servo-motor for valve positioning
N. Distance device & ceiling of room
O. Overfl ow connection ½"
P. Waste water trap
. Mains stop valve
F
G.
Brine storage
Cabinet
02/10/2012 09:48
EN
11