Herunterladen Inhalt Inhalt Diese Seite drucken

Safety; General Safety Instructions; Instructions, Standards And Regulations; Appliance Description - STIEBEL ELTRON AUK 7 Bedienung Und Installation

Gebläsekonvektor
Vorschau ausblenden Andere Handbücher für AUK 7:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

INSTALLATION

SAFETY

INSTALLATION
7.
Safety
Only qualified contractors should carry out installation,
commissioning, maintenance and repair of the appliance.
7.1

General safety instructions

WARNING Risk to life through electrocution!
Electrical components are 'live'.
»Before any cleaning and maintenance work, isolate
the appliance from the power supply.
WARNING Risk of injury through moving parts.
Fan motors can start automatically. Before opening
the casing, switch the appliance OFF and remove the
appliance fuse.
We guarantee trouble-free operation and operational reliability
only if the original accessories and spare parts intended for the
appliance are used.
7.2

Instructions, standards and regulations

Observe all applicable national and regional regulations
and instructions.
8.

Appliance description

The heating connections are located on the left and right side of
the appliance casing.
The electrical connections are located behind the swing door on
the right side of the appliance.
8.1

Standard delivery

- Fan convector
- Wall mounting bracket (hooked into the back of the appliance)
28
|AUK
287974-38519-9032.indb 28
9.
Installation
9.1

Installation location

When selecting the installation location, observe the critical
environmental factors that influence the use of the appliance.
Critical
Examples
environmental
factor
Air lightly or heavily
Factories producing
contaminated with dust.
cement, lime or
The heat exchanger will
gypsum
become clogged.
Warehouses
Hairdressing salons
Atmosphere containing
Sewage works
ammonia.
The heat exchanger will
If handling faeces
corrode.
Environments with
Machinery rooms
oil fog.
(lathe or milling work)
The heat exchanger will
become clogged.
- Only install the appliance in rooms free from the risk of frost.
- Only use the appliance in living spaces or similar areas.
- Only mount the appliance on vertical and load-bearing walls.
- Always install the appliance horizontally.
- Ensure that curtains, furniture and other objects do not cover
or restrict the air flow at the air inlet or air outlet grille.
- Do not install the appliance in wet areas.
- Observe the following minimum clearances during
installation:
*
* We recommend a floor clearance of 100 mm.
The back of the appliance must be fixed to the wall. Never install
the appliance on the floor.
Application
Usage only possible with
reduced maintenance
intervals
Usage only possible with
reduced maintenance
intervals
Usage only possible with
reduced maintenance
intervals
Use of the appliance is not
permissible
Use of the appliance is not
permissible
Usage only possible with
reduced maintenance
intervals
WWW.STIEBEL-ELTRON.COM
19.02.2015 12:05:18

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Auk 14Auk 21Auk 35Auk 28

Inhaltsverzeichnis