Step
Programming
Reset to factory settings
Resets all settings to the state on delivery. Before the fac-
tory reset check the possible effects on your application!
• Press the "Mode/Enter" button until rES is displayed
• Press the "Set" button and keep it pressed until
"- - - -" is displayed,
• Press the "Mode/Enter" button briefly.
Setting range for the probe length (applies to all LR70 type units)
Setting range
in steps of
The probe can be replaced. Probes are available as accessories in different
lengths.
Setting range for OFS (applies to all LR70 type units)
Setting range
in steps of
Setting range for SPx, rPx
LR7022 ( L = 24)*
cm
SPx
1.5...20.0
rPx
1.0...19.5
∆L*
0.5
*L = probe length [cm] on delivery; ∆L = increments
The values apply to the probe length on delivery and OFS = 0.
rPx is always smaller than SPx. Reducing the value for SPx to a value ≤ rPx
also shifts the position of rPx.
If the difference between rPx and SPx is small (approx. 3 x increment),
increasing rPx also increases SPx.
If the difference between rPx and SPx is great, rPx remains at the set value
38
The display then returns to rES.
15...70
0...100
inch
0.6...7.8
0.4...7.6
0.2
cm
0.5
cm
0.5
LR7023 (L = 45)*
cm
1.5...41.0 0.6...16.2
1.0...40.5 0.4...16.0
0.5
inch
6.0...27.6
inch
0...39.4
LR7024 ( L = 70)*
inch
cm
1.5...66.0 0.6...26.0
1.0...65.5 0.4...25.8
0.2
0.5
Parameter
0.2
0.2
inch
0.2