Herunterladen Inhalt Inhalt Diese Seite drucken

Dip Switch Posi T Ions - Honeywell ACC 50 Bedienungsanleitung

Zutrittskontrollsystem für bis zu 99 berührungslose karten
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Operating Instructions ACC50
5.
Position of the DIP switches
DIP switch 1 and 2
The period the door strike relay remains operated after an authorized card has been read or the
external door strike switch has been pushed can be determined with DIP switch 1 and 2.
DIP switch 3 and 4
The monitoring time is adjusted with DIP switche 3 and 4. The alarm relay is activated if the monitoring
time has run down and the status signal contact is still open.
Choose position "No" to disable the evaluation of the status signal contact.
DIP switch 5 and 8
The DIP switches 5 to 8 must be in "0" position.
Release time
(seconds)
3
8
12
20
1 = Switch ON
Shortly cut off the power supply when you have changed the DIP switch positions because the ACC
50 won't read in the DIP switch position unless the operating voltage is applied
Monitoring time
(seconds)
No
10
20
40
0 = Switch OFF
DIP switch
1
2
3
4
0
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
15

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis