Warning
The power supplies are constructed in accordance with the safety requirements of IEC 60950, EN60950, UL60950, UL508,
EN60204, EN50178, EN61558-2-8, IEC/EN/UL60079-15 (Protection Type "n" Class I, Zone 2, AEX nC II T4 U), ATEX 94/9/EC
(category 3; EEX nC II T4 U) and FM3611 (Class I and II, Division 2, Class III Division 1 and 2). They fulfil the requirements for
CE-compatibility and carry the CE-mark and are UL & cUL approved by CSA.
The TSP built-in power supplies were designed especially for use in process automation and other industrial applications.
To comply with IEC/EN/UL60079-15 the built-in power supply requires a EXD IEC60079-1 enclosure.
Components with dangerously high voltage and high stored energy are located in the device. However, these are inaccessible.
Failure to properly maintain the power supply can result in death, severe personal injury or substantial property damage. The
power supplies may o
regulations (e.g. UL, ANSI, VDE, DIN) must be observed. The successful and safe operation of this power supply is dependent
on proper storage, handling, installation and operation.
The potentiometer to adjust the output voltage is only allowed to be actuated using an insulated screwdriver, because
accidental contact may be made with parts inside the power supply carrying dangerous voltages.
Please observe following points before putting the device into operation:
Read operating instructions thoroughly.
That the mains connection has been carried out by a competent person and protection against electrical shock is
guaranteed!
That the device can be disconnected outside the power supply in accordance with the regulations as in IEC/EN/UL 60950
or other national regulations.
That the protective earth is connected.
That the input wiring is sufficiently protected and dimensioned!
That the output wiring is dimensioned according to the maximum output current or separately protected!
Sufficient cooling is guaranteed!
The temperature of the housing can become very high, depending on the ambient temperature and load.
Caution:
Risk of electrical shock and electrical discharge. The power supply must not be opened until at least 5 minutes after complete
disconnection of the mains.
Electrostatic sensitive device.
Attention: In case of non-observance or exceeding the mentioned limiting value of the data sheet, the function
and electrical safety can be impaired and can destroy the power supply.
Before installation ensure that the main switch is switched off and prevented from being
switched on again. In case of non-observance, touching of any live components or improper
dealing with this power supply can result in death or fatal injury.
1. Description and construction
The TSP power supplies are built-in units. The mounting position has to fulfil the requirements for fireproof case according to UL60950, IEC/EN
60950 or other appropriate national standard. The relevant UL regulations or equivalent national regulations must be observed during

installation.

The TSP power supplies are designed for mounting on a DIN rail TS35 (DIN EN 50022-35x15/7.5) and for operation from 115 or 230VAC,
50/60Hz (Universal input voltage range for TSP 070-112 and TSP 090-124, and auto range for TSP 140-112, TSP 180-124, TSP 360-124 und
TSP 600-124) single-phase systems.
The output voltage of the TSP power supplies is potential-free (floating), protected against short circuit and open circuit conditions (see Fig 1.1,
Fig 1.2 and Fig 1.3).
2. Installation
A sufficiently strong DIN-rail has to be provided. The correct mounting position for optimal cooling performance must be observed. Above and
below the power supply a minimum free space of 80mm [3.15in] is required and on each side of the power supply a minimum space of 50mm
[1.97in] is required which allows air convection. The air temperature measured 10mm [0.39in] below the power supply must not exceed the
specified values in the data sheet. Observe power derating above ambient temperatures of 40°C and at low line. (see Fig 4.1 and Fig 4.2)
2.1 Assembly
To fix unit on the DIN-rail, hook top part of clip on DIN-rail, push down- (see Fig 2.1) and inwards (see Fig 2.2) until you hear a clipping sound.
To remove the unit, pull the latch of the clip with the aid of an insulated flat head screwdriver (see Fig 2.3). When clip has cleared bottom DIN
rail remove the screwdriver from recess. Lift the unit off DIN-rail. See Fig 2.4.
Wall mounting or chassis mounting can be achieved by use of optional mounting brackets TSP-WMK01 (1 bracket, see Fig. 6.1) for TSP 070,
TSP 090, TSP 140 & TSP 180 or TSP-WMK02 (2 brackets, see Fig. 6.2 and Fig. 6.3) for TSP 360 & TSP 600. Remove the DIN-clips by
removing the screw and place the mounting brackets in the same place as the DIN-clips. Use the countersink screws which are included with
the wall mounting kit (1 countersink screw with TSP-WMK01 and 2 countersink screws with TSP-WMK02) to fix the mounting brackets on the
TSP power supply (tightening torque 0.8-0.9Nm).
nly be installed and put into operation by qualified personnel.
Qualified and trained personnel only may open the power supply.
Danger:
Never work on power supplies if power is applied!
Tel: +41 43 311 4511
Jenatschstrasse 1
Fax: +41 43 311 4545
CH-8002 Zürich
sales@traco.ch
Date:
www.tracopower.com
Issue: 2.1
English