Technical data
Interference dimensions
Required space above backflow preventer
Wall distance DN 65-100
Wall distance DN 150
Minimum inlet length (waste water) up to
the first change of direction
3
Installation
The backflow preventer BA must be installed
horizontally. Provide cut-off valves in front of
and behind the backflow preventer. To carry out
maintenance a drain valve with a hose connection
should be installed on the shut-off valve on the
supply side.
Note! In addition, a dirt trap must be
connected upstream which prevents
the backflow preventer from damage
and functional impairments due to
coarse dirt.
Install the backflow preventer free of tension and
without flexural moment as follows:
1.
Thoroughly rinse connecting pipe
Check connections on backflow preventer for
2.
cleanliness (Illustration 1)
3.
Install backflow preventer as in Illustration 2
© www.kemper-olpe.de – 11.2020 / K410036100002-00 – 20 / 28
mm
650
mm
160
mm
200
mm
600
Hinweis!
Flow in direction of arrow.
Maintain installation clearances.
Make sure there is good accessibility.
Make drain lines without any tight bends
and keep them short. Dimension the
wastewater connection to be sufficiently
large according to DIN EN 12056 and DIN
1986-100.
Install the drain line so that the drain con-
nection and the drain valve can be removed
for inspection.
A material-steadying zone of 5 x DN after
the BA is recommended.