Important notes
Safety instructions
-
Protect the unit against moisture, dirt and
damage during transport, storage and
operation.
-
Do not operate the unit outside the
specified technical data.
-
Operate only in a closed housing
(distribution cabinet).
-
Earth the unit at the terminals provided
for this purpose.
-
Do not obstruct cooling of the units.
- 17 -
Technical data
Connection
Inputs/outputs
2 connector strips,
each with 16 screw-
type terminals
Auxiliary voltage supply 1 connector strip
with 2 screw-type
terminals
ABB i-bus
®
EIB
Bus connection
terminal
Dimensions
(H x W x D)
90 x 72 x 64 mm
Mounting depth/width 68 mm
4 modules, 18 mm
each
Weight
0.170 kg
- 21 -
Technical data
The unit is used to connect pushbuttons or
signal lamps to ABB i-bus" EIB, e.g.: in an
operating/indicator panel. It features 32
inputs/outputs which can be freely
programmed with the aid of the ETS. The unit
requires an external auxiliary voltage supply
for powering the input/outputs. The bus
connection is made via the bus connection
terminal on the front side.
- 18 -
Commissioning/operation
The physical address, the group addresses
and the parameters are set with the ETS2
(EIBA Tool Software).
The ESD (Electrostatic Sensitive Device)
safety measures must be followed when
connecting the indicators and operating
controls on the UK/S32.1. It suffices for the
electrician performing the work to discharge
any body charges to earth potential before
starting work.
In order to avoid electrostatic discharges to
the unit during use of the UK/S32.1 as
intended, please ensure that no conductive
parts connected to the input or output
terminals of the unit can be touched directly.
- 22 -
Technical data
Power supply
via ABB i-bus
®
EIB
Auxiliary voltage supply
Rated value
12/24 VDC
Permitted Voltage range 10...30 VDC
Rippel
< 5 %
Current consumption
2,8 A at full load
Inputs/outputs
Number
32,freely programm-
able as input or
output
Permitted line length
- 10 m
Input
Sampling voltage
24 VDC
Output
Supply voltage
24 VDC
- 19 -

Installation

For installation in distributors or in operating/
indicator panels. Snap-on mounting on 35
mm mounting rail DIN EN 50022.
The bus connection is made by plugging on
the bus connection terminal (included in
scope of delivery).
The input/outputs are connected via
connector strips with screw-type terminals.
Wire range 0,14-1,0 mm
2
.
Should the LEDs glow slightly when they are
OFF, this can reduced to a minimum by
lowering the supply voltage from 24 V to 12 V.
- 23 -
Technical data
Output current
8 mA per output
700 mA per group of 8
2.8 mA per unit
(T
= 25°C)
u
Load type
Resistive
Safety
Short circuit-proof,
overload protection,
reverse-voltage
protection
Operating controls and indicators
LED (red) and key
for entry of the
physical address
Label mount
Enclosure
IP 20 to DIN 40050
Safety class
II
Operating temperature
range
-5...45 °C
- 20 -
- 24 -