Herunterladen Inhalt Inhalt Diese Seite drucken

General Data - Motus 36112 Betriebsanleitung

Hybrid-motorstarter mit wendefunktion
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 6
Variants

General data

Power dissipation min. / max.
Max. switching frequency (pulse / pause times 50:50)
Deactivation time via control supply voltage
Deactivation time via activation voltage
Activation time via activation voltage
Rated surge voltage between control input, control supply
and switching voltage
Nominal mains voltage (≤ 500V AC)
Nominal mains voltage (≤ 300V AC), e. g. 230 / 400V AC,
277 / 480 V AC
Nominal mains voltage (≤ 300 – 500V AC)
Control input, control supply voltage and reply output,
reply output and switching voltage
Nominal mains voltage (≤ 500V AC)
Nominal mains voltage (≤ 300V AC), e. g. 230 / 400V AC,
277 / 480V AC
Nominal mains voltage (≤ 300 – 500V AC)
Ambient temperature range operation
Ambient temperature range transport, storage
Surge voltage category
Pollution degree
Standards/specifications
Power station requirement
Service life
Degree of protection
Mounting position
Mounting (see 9. Derating curve)
Housing:
Material
Dimensions incl. DIN rail adapter
Dimensions incl. power busbar adapter 30Compact
Dimensions incl. power busbar adapter 60Classic
Connection data (conductor cross-section)
Screw terminal blocks (solid / stranded)
M3 thread, recommended torque
Adapter connection data
Connection Ø DIN rail adapter (solid / stranded)
Copper Ø Compact / Classic power busbar
Max. power busbar current
Weight
DIN rail adapter
6Power busbar adapter 30Compact
Power busbar adapter 60Classic
Certification
EC type examination certificate to ATEX
Safety level
Contact · Wöhner GmbH & Co. KG · Elektrotechnische Systeme · Mönchrödener Straße 10 · D-96472 Rödental
Postal address PO Box 11 60 · D-96466 Rödental · Germany
Telephone +49 (0) 9563/751-0 · Fax +49 (0) 9563/751-131 · info@woehner.com · www.woehner.com
28
Max. 0.6A
Max. 2.4A
0.88W / 2.8W
0.88W / 5.5W
type 25ms
type 30ms
type 40ms
Safe isolation (EN 50178)
Safe isolation (IEC 60947-1)
Basic isolation (IEC 60947-1)
Safe isolation (IEC 60947-1)
Safe isolation (EN 50178)
Safe isolation (IEC 60947-1)
Basic isolation (IEC 60947-1)
– 25°C – + 70°C
– 40°C – + 80°C
IEC 60947-4-2 / IEC 61508-1 / ISO 13849-1/EN 954-1
DWR 1300 / ZXX01/DD/7080.8d
3 × 10
Vertical (horizontal DIN rail / busbar)
Can be mounted in rows with zero spacing or with ≥ 20mm spacing
(22,5 / 175 / 138)mm (W/H/D)
(22,5 / 160 / 156)mm (W/H/D)
(22,5 / 200 / 156)mm (W/H/D)
See connection notes (page 22)
0.14 – 2.5mm²
0.5 – 0.6Nm
0.2 – 6mm² / 0.2 – 4mm² (AWG 24–10)
5 (or 10) × 12mm / 5 (or 10) × 30mm
Approx. 368g
Approx. 374g
Approx. 377g
EX II (2) G [Exe] [Exd] [Expx]
PTB 13 ATEX 3001
See section 8.1 and 8.2
Max. 9A
0.88W / 12W
2Hz
max. 500ms
max. 80ms
max. 50ms
6kV
III
2
7
cycles
IP20
PA 6.6
AWG 26–14
4.4 – 5.3 lb-in
2500A
EX II (2) D [Ext] [Exp]

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

3611436100361113610836109

Inhaltsverzeichnis