3. Mounting and connecting
the main circuit
Snap the complete module including busbar or DIN rail
adapter onto the rail.
Click
Click
Click
In the case of the busbar variant, the electrical connec-
tion to the 3-phase network is established directly by
means of the adapter. When using the DIN rail adapter,
observe the terminal designations when connecting
the 3-phase network.
CAUTION: Never carry out work when voltage is
present! Danger to life!
Revision 6, status 05.2017
The following coordination types are achieved with the
fuses used:
Coordination types
0.6A and 2.4A variants
16A
10kA, 500V, coordination types 2
(FUSE-10X38-16A-GR)
device protection
50kA, 500V, coordination type 1
system protection
9A variants
20A
5kA, 400V, coordination types 2
(FUSE-10X38-20A-GR)
device protection
50kA, 500V, coordination type 1
system protection
30A
30kA, 500V, coordination type 1
(FUSE-ClassCC-30A-MR)
system protection
Note: 30A fuse is only needed for motors with heavy
starting.
Removal
To remove the busbar variants, the electronicscom-
ponent must f irst be removed from the busbar
adapter.
1.
2
2.
2