AWG | Fittings | Medium expansion foam nozzle M2, M4, M8
After use: Rinsing and uncoupling the foam nozzle
1. Shut off the water supply.
2. Interrupt the supply of foam agent.
3. Open the water supply and, if applicable, the hand lever.
4. As soon as only clear water and no more extinguishing foam emerges
from the foam tube, close the hand lever or stop the water supply,
respectively. If necessary, perform multiple rinsing passes.
5. Shut off the water supply.
6. Open the foam nozzle to reduce the pressure.
Attention Water will emerge when opening the foam nozzle.
7. Detach the coupling of the water hose (Fig. 2/6) from the fixed cou-
pling on the foam nozzle (Fig. 2/5) by hand or with the use of a cou-
pling spanner.
Attention Water may emerge when the couplings are released.
5 .3
Visual inspection after each use
The foam nozzle is separated from the water supply.
9
The foam nozzle must not be contaminated with foam agent. If neces-
9
sary, rinse the foam nozzle again as described in the previous section.
Attention Do not continue to use damaged components! If you dis-
1. Inspect the foam nozzle for visible damage.
2. If the device is equipped with a hand lever (option), check that it can
be operated (unpressurised).
33
cover any damage, this must be reported to the person or
department responsible.
USE
M1107B10 | Rev. 03-08/24