Parameter list HART® for FMX-IM-2UPLi63X
4
electrical connection
The cable is connected via reverse polarity protected terminal blocks with undetachable screws for the connection widths
≤ 1 × 2.5mm², 2 × 1.5mm² or 2 × 1mm² with wire end sleeve.
IMPORTANT INFORMATION
Distances between device and sensor
The length of the interconnection between the flow sensor and the device may be max. 100 m. With lengths exceeding
30 m a shielded sensor cable is recommended. In either case, it should be checked whether the chosen wire width meets
the requirements.
Function
Sensor Supply
heated Pt1000
GND
unheated Pt1000
Voltage Supply
PNP 1 (Out 1)
PNP 2 (Out 2)
PNP 3 (Out 3)
1 (Out 1)
Relay
2 (Out 2)
Relay
3 (Out 3)
Relay
Current Source
HART®
Table 1
Terminal assignment
4.1
Block diagram
FMX-IM-2UPLI63X
BN
1
+ 1
WH
2
2
BU
3
3
BK
4
4
Figure 1
Block diagram HART®-device
4
FM(X)-IM-2UPLi63X
Terminal 1
Terminal 2
Terminal 3
Terminal 4
Terminal 19 (+)
Terminal 20 (−)
Terminal 13
Terminal 14
Terminal 11 (+)
Terminal 16 (−)
Via terminals 11 and 16, alternative via female connector COM (PC)
COM (PC)
11
Flow/
0/4...20 mA
R L £ 600 W
16
YE
13
2 Temp
£ 30 V
£ 100 mA
RD
14
3 Fault
19 +
Pwr
20...30 VDC
GN
20
Hans Turck GmbH & Co. KG • Tel. +49 (0) 208/4952-0 • Fax +49 (0) 208/4952-264