6. TECHNICAL DATA

meas. input
Designation
Resistance
pt100 eN 60 751
thermometer
pt1000 eN 60 751
KTY2X-6 (pTC)
measuring current with pt100: 0.2 ma, with pt1000 and KTY2X-6: 0.02 ma.
lead compensation is settable via the parameter lead compensation resistance
Total resistance (sensor+lead) must not exceed 320Ω with pt100.
Current
0 to 20 ma
4 to 20 ma
input resistance r
≤ 3Ω
iN
20 / 72
Range
–200 to +600°C
–200 to +600°C
50 to +150 °C
–2 to 22 ma scalable
S.cL
with
and
or customer table
2.4 to 21.6 ma
scalable with
S.cH
and
Raychem-IM-INSTALL100-TCONCSD20-EN-1703
meas. accuracy
ambient
temperature error
0.1%/ ≤100ppm/°C
0.1%/ ≤100ppm/°C
1%/ ≤100ppm/°C
Of.r
0.1%/ ≤100ppm/°C
S.cH
0.1%/ ≤100ppm/°C
S.cL
INDUSTRIAL HEAT TRACING SOLUTIONS
/
Recognition of ...
1
probe
probe
shortcircuit
break
Yes
Yes
Yes
Yes
Yes
Yes
.
No
No
3
Yes
Yes
3

Werbung