Herunterladen Diese Seite drucken

IFM Electronic Efector300 VS 0200 Bedienungsanleitung Seite 5

Schaltverstärker

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Adjustment
(K1) = measuring circuit 1
(K2) = measuring circuit 2
1 = hain of LED's
- red LED lights: the unit is not
adjusted
- yellow LED lights: the relay is
energised
- green LED lights: the unit is adjusted
2 = setting potentiometer
sensitivity
3 = red LED
- lights in case of wire break or short circuit
- lights in case of temperature exceeding
4 = potentiometer temperature monitoring
5 = slide switch (medium)
liquids
gases
Operation: The operation of the VS0200 is
maintenance-free.
In the case of an open circuit or short circuit the
relay "wire monitoring" is de-energised and
the red LED is lit. When this fault has been
5
(K1)
(K2)
liquids
gases
1
1
2
2
(K1)
3
3
4
Temp. / temp.
40
1
2
20
(K2)
3
4
1. Set the selector switch (5) to liquids or gases
2. Apply the operating voltage. Switch on the
flow (preset value) and keep it constant.
→ The yellow LED and one green LED light;
the output relay is energised for about 30 s
(power-on delay time).
3.Turn the pot (2) until one green LED comes
on.
The farther the green LED is away from the
yellow LED, the safer is the adjustment (ex-
cess gain for flow or temperature fluctuations).
rectified, the control monitor is again ready for
operation.
1
2
3
4
5
6
7
Temp. / temp.
Strömung / flow
Relais /
Relais /
relay
relay
VS 0200
Strömung / flow
60
80
1
2
°C
+
1 Flüssig /
liquid
ifm electronic
2 Gas / gas
D 45127 Essen
9
10
11 12 13 14 15 16
4
5
8
+

Werbung

loading