Herunterladen Diese Seite drucken

IFM Electronic efector 600 TN2530 Bedienungsanleitung Seite 23

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Lower end of analogue output
Measured value for which the output signal is 4 mA / 0 V.
Upper end of analogue output
Measured value for which the output signal is 20 mA / 10 V.
Minimum distance between ASP - AEP: 10°C / 18°F.
Setting range:
°C
-40 ... +115
°F
-40 ... +239
Output function for the analog output
2 options can be selected:
I = 4 ... 20 mA / U = 0 ... 10 V
Setting of the display
4 options can be selected:
°C = display in °Celsius
°F = display in °Fahrenheit
r°C = display in °Celsius (inverted)
r°F = display in °Fahrenheit (inverted)
Select the display unit before setting the switch points (SP1,
rP1) and the limits for the analog output signal (ASP, AEP). This
avoids rounding errors generated internally during the conver-
sion of the units and enables exact setting of the values.
Units are delivered from the factory with dis = °C
Calibration offset
The internal measured value (operating value of the sensor) is
offset against the real measured value.
°C
°F
Min-Max memory for system temperature
• Hi: displays the highest measured temperature
• Lo: displays the lowest measured temperature
Erase the memory:
- Press the "Mode/Enter" button until HI or Lo is displayed.
- Press the "Set" button and keep it pressed until "- - -"
is displayed.
- Then press the "Mode/Enter" button briefly.
It is recommended to erase the memory as soon as the unit
starts working under normal operating conditions.
ASP
-30 ... +125
-22 ... +257
setting range
-9.9 ... +9.9
-17.5 ... +17.5
AEP
in steps of
in steps of
0.5
1
0.1
0.5
23