Installation and set-up / operation
Check the safe functioning of the unit. The operation is maintenance-
free. Failure indication:
Too high a temperature.
Too low a temperature
Flashing: Short-circuit in the switching output (OUT 1).
The output is switched off as long as the short circuit continues.
Technical information / Functioning / Parameters
Adjustable parameters
Switch-on point: Upper limit value at which the output
changes its switching status.
Switch-off point: Lower limit value at which the output
changes its switching status.
rP1 is always lower than SP1. The unit only accepts values which
are lower than SP1.
Changing the switch-on point also changes the switch-off point
(the hysteresis remains constant).
If the hysteresis is higher than the new switch point, it is auto-
matically reduced (rP1 is set to the minimum setting value).
Setting range:
Configuration of the switching output
4 switching functions can be set:
22
°C
-39.5 ... +125
°F
-39 ... +257
Hno = hysteresis / normally open
Hnc = hysteresis / normally closed
Fno = window function / normally open
Fnc = window function / normally closed
SP1
-40 ... +124.5
-40 ... +256
rP1
in steps of
0.5
1