Herunterladen Diese Seite drucken

Danfoss AMV213 Bedienungsanleitung Seite 37

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

7 Adjustments AME210, AME213
Prior to commissioning, the input and output signals must be adjusted and
the end positions must be aligned.
7.1 Overview DIP switch settings
ON
OFF
1
1
Without function
2
Input signal
3
Output signal
4
Inverse operation
5
Automatic operation
6
Manual operation:
Extend stem
7
There is no new alignment of
the end positions
8
Fault indicator ON
1)
During control operation, it is absolutely necessary to set switch to
automatic.
The switch positions 1, 6, 7, 8 have no influence on normal control
operation.
2 3 4 5
6 7 8
4 - 20 mA
2 - 10 V
2 - 10 V
20 mA
10 V
0(2, 4)
0
Hub
100 %
1)
Adjustments AME210, AME213
ON
ON
1
2 3 4 5
Without function
Input signal
Output signal
20 mA
10 V
Normal operation
0(2, 4)
Manual operation
Manual operation:
Retract stem
When switching on the po-
wer supply, the stem is ex-
tended until the valve is
closed,
End position „Valve closed"
is re-aligned.
Fault indicator OFF
6 7 8
0 - 20 mA
7.2
0 - 10 V
0 - 10 V
7.3
7.4
0
Hub
100 %
8.3
8.3
-
9.3
37