Mounting
5.2 Mounting the Actuator on
the Valve
Prior to mounting, please observe:
DANGER: High voltage !
Danger to life or injury in case of
unqualified handling. Actuator
can be damaged.
Prior to mounting, switch off
voltage supply when connecting
an electrical actuator.
1. Put actuator on the valve.
2. Unscrew union nut
fasten with wrench SW 36,
torque 35 Nm.
30
1
and
1
3. Loosen Philips screws (4x)
and remove cover.
It is absolutely necessary to re-
move the mounting aid (pin with
yellow head) !
If the pin is not removed, the
actuator is blocked.
4. Connect electrical lines
(see next section).
Pin