6 Mechanical Stroke
Setting
The stroke of the electrical
actuator (maximum stroke 15 mm)
must be adjusted after having
mounted the valve stroke.
This avoids an „empty" stroke of
the actuator and a possibly unsta-
ble control.
Prior to mounting, please observe:
DANGER: High voltage !
Danger to life or injury in case of
unqualified handling. Actuator
can be damaged.
It is absolutely necessary to
disconnect power supply prior
to setting the stroke.
6.1 Valve Types VIG2, VIS2,
VIU2, AIQM
1. Ensure that power has been
disconnected.
2. Close valve (open VIU2)
VIG2, VIS2,
AIQM
VIU2
Mechanical Stroke Setting
AMV213, AME213
The valve automatically closes
(VIU2 opens) when the power
is disconnected, proceed with
item 3.
AMV210, AME210
Loosen Philips screws (4x)
l
an remove cover.
Turn stem
1
l
with an hexagon socket screw
key until you feel resistance.
➻ ➻ ➻ ➻
The valve is closed
(VIU2 is open).
with low force
1
33