INSTALLATION INSTRUCTIONS FOR
MODULES AND TC809E1068 INPUT /
This manual is intended as a quick reference installation guide. Please refer to the control panel
manufacturers installation manual for detailed system information
GENERAL INFORMATION
The M200 series of modules are a family of microprocessor controlled interface devices
permitting the monitoring and/or control of auxiliary devices.
SPECIFICATIONS
Operating Voltage Range
Maximum Standby Current (µA)
No Communications
Communication with LED enabled
LED Current (Red)
LED Current (Yellow)
Operating Temperature
Humidity
Module Dimensions
Surface Mount Box Dimensions
Weight (Module Only)
Weight (Module and M200E-SMB)
Maximum Wire Gauge
INSTALLATION
Note:
These modules must only be connected to control panels using compatible proprietary
analogue addressable communication protocols for monitoring and control.
M200 series modules can be mounted in several ways (See figure 1):
1.
An M200E-SMB custom low profile surface-mounting box.
2.
An M200E-DIN Adaptor allows mounting onto standard 35mm x 7.5mm "Top Hat" DIN rail.
3.
An M200E-PMB Panel Mount Bracket allows the module to be mounted directly into a panel.
Wiring to all series M200 modules is via plug in type terminals capable of supporting conductors
up to 2.5mm²
Disconnect loop power before installing modules or sensors
The module address is selected by means of rotary decade address switches (see figure 2).
These can be accessed either from the front or the top of the module. A screwdriver should be
used to rotate the wheels to select the desired address, either from the front, or the top of the
module.
For modules having more than one channel, the address selected will refer to the first input
channel, the module will automatically assign the next one or two addresses as appropriate to the
second input channel and output channel. As a result, address 99 will be invalid for dual channel
modules, and addresses 98 and 99 are invalid for three channel modules. If these addresses are
selected, no response will be seen from the module.
Short Circuit Isolators
All M200 series modules are provided with short circuit monitoring and isolators on the intelligent
loop. If required the isolators may be wired out of the loop to facilitate the use of the modules on
high current loaded loops, for example if sounders are used. To achieve this, the loop out positive
should be wired to terminal 5 rather than terminal 2. See the relevant wiring diagram for details.
FIGURE 1: MODULE MOUNTING METHODS
M200E-SMB Surface Mount Box
COVER
Surface Mount Box
Base is affixed to
mounting surface, and
MODULE
then the module and
cover are screwed
onto the base using the
two screws supplied.
BASE BOX
FIGURE 3: TC809E1043 SINGLE INPUT AND TC809E1050 DUAL
INPUT MODULE WIRING
-
LOOP OUTPUT
+
LOOP OUTPUT
-
LOOP INPUT
+
LOOP INPUT
+
LOOP OUTPUT (SEE NOTES 1)
47KΩ
47KΩ
M200-EOL-R
M200-EOL-R
(SEE NOTES 2)
Notes:
1
If short circuit isolation is not required, loop output+ should be wired to terminal 5 and not
2. Terminal 5 is internally connected to terminal 4.
2
The dashed line circuit connected to terminals 8 and 9 should only be used with the
TC809E1050. There are no connections to these terminals on the TC809E1043.
3
Provided the control panel is compatible, short circuit monitoring of the input circuit may
be possible. An 18KΩ resistor should be wired in series with each device switch being
monitored.
H200-91-00
TC809E1043 / TC809E1050 INPUT
OUTPUT MODULE
15 to 30VDC (Min 17.5VDC to ensure LED operation)
TC809E1043
TC809E1050
TC809E1068
310
340
340
510
600
660
2.2mA
8.8mA
-20°C to 60°C
5% to 95% Relative Humidity
93mm(H) x 94mm(W) x 23mm(D)
132mm(H) x 137mm(W) x 40mm(D)
110 g
252 g
2.5mm²
CAUTION
M200E-DIN DIN Rail Bracket
TOP
BOTTOM
TC809E1043
TC809E1050
4
5
3
6
2
7
1
8
0
9
A
x10
B
Pittway Tecnologica SpA, Via Caboto 19/3, 34147 TRIESTE, Italy
TC809E1043 SINGLE CHANNEL INPUT MODULE
Provides single channel monitoring of normally open contact fire alarm and supervisory devices.
The TC809E1043 has a single tri-colour green/red/yellow LED, which can be set by panel
command to pulse green each time the module is polled. In case of an alarm the panel can switch
the red indicator on continuously. The Yellow LED is controlled by the module and blinks to
indicate an open circuit on the input circuit. This fault indication is overridden by a panel
command to turn the red LED on.
TC809E1043 Wiring
See figure 3 for wiring details.
TC809E1050 DUAL CHANNEL INPUT MODULE
The TC809E1050 is a dual channel module used for the monitoring of normally open contact fire
alarm and supervisory devices.
It has two tri-colour LED's, one referring to each channel. Each LED can be set by panel
command to pulse green each time the module channel is polled. In case of an alarm the panel
can switch the red indicator on continuously. The Yellow LED is controlled by the module and
blinks to indicate an open circuit on the input circuit. This fault indication is always overridden by
a panel command to turn the red LED on.
TC809E1050 Wiring
See figure 3 for wiring details.
TC809E1068 DUAL INPUT, SINGLE OUTPUT MODULE
This module provides dual channel monitoring of normally open contact fire alarm and
supervisory devices, and also provides single pole changeover contacts for the control of auxiliary
devices such as fire shutters.
Three tri-colour LED's are provided to indicate the status of each channel.
LED's A and B refer to the two input channels. Each LED can be set by panel command to pulse
green each time the module channel is polled. In case of an alarm the panel can switch the red
indicator on continuously. The Yellow LED is controlled by the module and blinks to indicate an
open circuit on the input circuit. This fault indication is always overridden by a panel command to
turn the red LED on.
LED C refers to the output channel. The LED can be set by panel command to pulse green each
time the channel is polled. The LED will be switched continuously on Green by command from
the control panel when the relay contacts are in the energised state.
The TC809E1068 relay contact ratings are 30VDC, 2A or 30VAC, 0.5A (Resistive load).
TC809E1068 Wiring
See figure 4 for wiring details
When switching inductive loads, in order
to protect the module from surges
caused by back emf as the load is
switched, it is important to protect the
A diode with a reverse breakdown voltage
of at least ten times the circuit voltage (dc
applications only), or a varistor (ac or dc
applications) should be connected across
M200E-PMB Panel Mount Bracket
Push Module into
adaptor Bracket until it
clips into place.
Locate top clip over
DIN rail and rotate
bottom down to clip
into place.
To Remove, lift up,
then rotate top away
from the rail.
FIGURE 4: TC809E1068 DUAL INPUT SINGLE OUTPUT MODULE WIRING
LOOP OUTPUT
LOOP OUTPUT
LOOP INPUT
LOOP INPUT
A B
LOOP OUTPUT (SEE NOTES 1)
1
0
4
5
3
6
2
7
1
8
0
9
x1
C
47KΩ
M200-EOL-R
Notes:
1
If short circuit isolation is not required, loop output+ should be wired to terminal 5 and not 2.
Terminal 5 is internally connected to terminal 4.
2
Provided the control panel is compatible, short circuit fault monitoring of the input circuit may
be possible. An 18KΩ resistor should be wired in series with each device switch being
monitored.
1
WARNING:
relay contacts.
the load.
Adaptor bracket is
mounted directly into
panel using 2 x M4
Pan head screws.
Module is pushed into
adaptor until it clips
into place.
-
+
-
+
+
47KΩ
NC
C
NO
M200-EOL-R
RELAY CONTACT RATING:
30VDC 2A OR 30VAC, 0.5A
RESISTIVE LOAD
CONTACT
DIODE
+
(DC
ONLY)
OR
VARISTOR
FIGURE 2: ROTARY DECADE
ADDRESS SWITCHES
A B
TC809E1068
1
0
4
5
4
5
3
3
6
6
2
7
2
7
1
1
8
8
0
9
0
9
A
x10
B
x1
C
I56-2058-002

Werbung

loading

Inhaltszusammenfassung für Honeywell TC809E1043

  • Seite 1 Provides single channel monitoring of normally open contact fire alarm and supervisory devices. TC809E1043 / TC809E1050 INPUT The TC809E1043 has a single tri-colour green/red/yellow LED, which can be set by panel MODULES AND TC809E1068 INPUT / command to pulse green each time the module is polled. In case of an alarm the panel can switch OUTPUT MODULE the red indicator on continuously.
  • Seite 2 MODULI DI INGRESSO TC809E1043/ con contatti normalmente aperti. TC809E1050, E DEL MODULO DI Il modello TC809E1043 è dotato di un singolo LED tricolore (verde/rosso/giallo) che può essere INGRES SO/USCITA TC809E1068 impostato con un comando del pannello affinché lampeggi di luce verde ogniqualvolta il modulo viene interrogato.
  • Seite 3 TC809E1050, Y EL MÓDULO DE ENTRADAS / El TC809E1043 tiene un solo LED de tres colores (verde/rojo/amarillo) que se puede configurar SALIDA TC809E1068 desde el panel para que el led verde parpadee cada vez que se interrogue al módulo. En caso de alarma, el panel puede hacer que el led rojo permanezca encendido de forma fija.
  • Seite 4 Schliesserfunktion oder Überwachungskontakten zur Verfügung. UND TC809E1068 Das TC809E1043 besitzt eine 3-farbige grün/rot/gelb LED, die bei jeder Kommunikation mit der Diese Kurzbedienungsanleitung ermöglicht einen schnellen Überblick zur Installation der Module. Zentrale grün aufblinkt. Im Alarmfall kann von der Brandmelderzentrale zur Anzeige die rote LED Für detaillierte Informationen lesen Sie bitte in der Installationsanleitung der Brandmelderzentrale.