4.4 Requirement for supply lines and fuse
PV-side
Max conductor cross-section
Min conductor cross-section
Connector type
Recommended cable type
AC-side
Max cable diameter
Min cable diameter
Length of cable jacket to be
stripped off
Max. conductor cross-section
Min. conductor cross-section
Length of conductor insulation to
be stripped off
Tightening torque
Connector type
Additional ground wire
Max. conductor cross-section for
additional ground conductor
connection
Min. conductor cross-section for
additional ground conductor
connection
Colour of cable
Interfaces
RS485 connection type
Terminal conductor cross-section
Ethernet cable type
RCR & NS Protection connection
type
RCR&NS Protection cable type
Page 89
6 mm
2
(copper)
2.5 mm
2
(copper)
Phoenix
Solar cable
42 mm
28 mm
130 mm
70 mm²
30 mm²
40 mm
12 Nm
DT / OT
6 mm
2
(copper)
6 mm
2
(copper)
Yellow - green
Twisted pair cable with shield
0.2 – 0.5 mm
2
Category 5
RJ45
Category 5