10.1 Current measurement "A"
Notes:
– For best results, conductors should be centered in the clamp.
– The current sensing clamp is magnetized and a low reading may appear
even when no conductor has been covered.
– Only one conductor should be covered by the current sensing clamp.
Tips:
50
For low currents, you can increase the field
strength to a measurable level:
1. Wind the conductor around one side of the
current clamp as shown.
2. Take note of the measured current.
3. Divide the measured current by the number of
winds (coils).
à
The real current has been derived.