Herunterladen Diese Seite drucken
Honeywell esser 808611.10 Installationsanleitung
Honeywell esser 808611.10 Installationsanleitung

Honeywell esser 808611.10 Installationsanleitung

Werbung

Installationsanleitung
®
esserbus
-Koppler 32 Optokoppler
Installation Instruction
esserbus
®
transponder 32 Optocoupler
(Art.-Nr. / Part No. 808611.10)
Technische Änderungen vorbehalten!
798848.10
Technical changes reserved!
D
GB
05.2015 / AA
© 2015 Honeywell International Inc.
Novar GmbH a Honeywell Company
Dieselstraße 2, 41469 Neuss, Germany
Tel.: +49 2131 40615-600
Fax: +49 2131 40615-606
www.esser-systems.com
info@esser-systems.com
150
107
Abb. 1: Maße und Befestigungslöcher (mm)
Fig. 1: Dimensions and fixing holes (mm)
32OC-Koppler
808611.10
1108
VdS G 206044
Abb. 2: Kennzeichnung
Fig. 2: Identification
Achtung!
Diese Installationsanleitung ist vor der Inbetriebnahme genau
durchzulesen. Bei Schäden die durch Nichtbeachtung der Anleitung
verursacht werden, erlischt der Gewährleistungsanspruch.
Für Folgeschäden, die daraus resultieren, wird keine Haftung
übernommen.
Allgemein / Anwendung
Dieser esserbus
die ESSER-Brandmelderzentralen geeignet.
Systemvoraussetzungen
BMZ / Koppler
800x
Compact
*1
IQ8Control
FlexES Control
®
esserbus
-
Koppler
*1
Zur Anschaltung an diese BMZ ist der Spannungskonverter
(Art.-Nr. 781336) erforderlich!
Systemgrenzen
max. 100 esserbus
max. 32 esserbus
max. 32 esserbus
Anschlussklemmen
Zur vereinfachten Installation können die Anschlussklemmen mit
einem geeigneten Werkzeug, z.B. Spitzzange abgezogen werden.
Nach dem Anschluss der Leitungen wird die Klemmenleiste wieder
auf die Steckkontakte aufgesteckt.
Länge der LED-Anschlussleitung je Ausgang:
max. 100 m
max. 3 m
Anschlusskabel
Fernmeldekabel I-Y (St) Y n x 2 x 0,8 mm mit besonderer
Kennzeichnung oder Brandmeldekabel verwenden!
Durch den Anschluss der Kabelabschirmung werden die
Signalleitungen gegen Störeinflüsse geschützt!
Spannungsversorgung / Überwachung
Der esserbus
10 V DC bis 15 V DC beschaltet und mit der Betriebsart
>überwacht< programmiert werden. Eine Unterbrechung oder das
Unterschreiten der zulässigen Toleranzgrenze (-10%) löst eine
Störungsmeldung an der Brandmelderzentrale aus.
Kennzeichnung (Abb. 2)
Den beiliegenden Aufkleber  auf dem Kopplergehäuse  (siehe
Pfeile in Abb. 2) aufbringen.
Einstellung der Betriebsart
Folgende Betriebsarten sind für jeden Optokoppler-Ausgang wählbar:
plus schaltend
minus schaltend  Innenwiderstand Ri = 1 kΩ
plus schaltend
minus schaltend  Innenwiderstand Ri = 0 kΩ
Programmierung des Schaltverhaltens
808611.10
Das Schaltverhalten der Optokopper-Ausgänge 1 bis 32
(plus- / minus- schaltend) ist in den Kundendaten individuell
programmierbar.
Technische Daten
Ringleitung
Nennspannung
Nennstrom
Externe Spannungsversorgung
Betriebsspannung
Ruhestrom
LED-Ausgang
Eigenschaften
Schaltverhalten
Länge der Anschlussleitung
1
Umgebungstemperatur
Lagertemperatur
Luftfeuchte
Schutzart
Gewicht
Maße (B x H x T)
Spezifikation
VdS-Anerkennung
2
Leistungserklärung
D
®
-Koppler ist ausschließlich für den Anschluss an
Programmiersoftware
Systemsoftware
tools 8000
ab Version V2.42.6
ab Version V1.19
ab Version V2.05
ab Version V1.20
ab Version V3.09
ab Version V1.15
*1
ab Version V04.01
ab Version V1.16
ab Version V3.01
ab Version V1.15
®
-Koppler pro Brandmelderzentrale
®
-Koppler pro Ringleitung
®
-Koppler pro Meldergruppe
 Innenwiderstand Ri = 1 kΩ
 Innenwiderstand Ri = 0 Ω
®
-Koppler kann mit einer externen Spannung von
 Innenwiderstand Ri = 1 kΩ
 Innenwiderstand Ri = 0 kΩ
: 8 V DC ... 42 V DC
: ca. 50 µA @ 19 V DC
: 10 V DC ... 15 V DC
: ca. 3 mA @ 12 V DC
: 12 V DC / 10 mA
: plus-/minus- schaltend
: max. 100 m (wenn Ri = 1 kΩ)
: max. 3 m (wenn Ri = 0 Ω)
: -10 °C ... +50 °C
: -25 °C ... +75 °C
:  95 % rel. Feuchte
(ohne Betauung)
: IP 40 (im Gehäuse)
: ca. 95 g
: 150 x 82 x 20 (mm)
: EN 54 - 17:2005/-18:2005
: G 206044
: DoP-20611130701
Ergänzende und aktuelle Informationen
Die Produktangaben entsprechen dem Stand der
Drucklegung und können durch Produktänderungen,
geänderte Normen/Richtlinien ggf. von den hier
genannten Informationen abweichen. Aktualisierte
Informationen und Konformitätserklärungen siehe
www.esser-systems.com.
Dokumentation der Brandmelderzentrale bzgl.
Normen, lokalen Anforderungen und
Systemvoraussetzungen beachten!
esserbus
®
und essernet
®
sind in Deutschland
eingetragene Warenzeichen.
Weiteres Zubehör siehe Produktgruppenkatalog
Brandmeldetechnik.
GB
Warning!
These installation instructions must be studied carefully before
commissioning. Claims under warranty will be invalidated in the
event of damage caused by non-compliance with the instructions.
No liability is accepted for any resulting consequential loss.
General / Application
®
This esserbus
transponder is designed for operation only with
the ESSER Fire Alarm Systems.
System requirements
FACP /
System software
transponder
800x
from Version V2.42.6
Compact
*1
from Version V2.05
IQ8Control
from Version V3.09
FlexES Control
*1
from Version V04.01
®
esserbus
from Version V3.01
transponder
*1
The DC / DC converter (Part No. 781336) is required for this
FACP connection.
System restrictions
max. 100 transponders per fire alarm control panel
max. 32 transponders per loop
max. 32 transponders per detector zone
Terminals
For easy installation the terminals may be removed with a suitable
tool, such as needle-nose pliers. When the loops have been
connected, attach the terminal strip to the plug contact again.
Length of LED connection cable per output:
max. 100 m
 internal resistance Ri = 1 kΩ
max. 3 m
 internal resistance Ri = 0 Ω
Connection cable
Use cable I-Y (St) Y n x 2 x 0,8 mm with special
designation or fire detection cable!
The shielding must be connected for EMI protection of
the communication cable!
Power supply / Supervised
External voltage 10 V DC to 15 V DC can be connected to the
esserbus
®
transponder and may be programmed in >supervised<
mode. An interruption of the supply voltage or voltage drop below
the permitted tolerance level (-10%) will cause a fault message of
the fire alarm control panel.
Identification (Fig. 2)
The supplied adhesive label  must be placed onto the
transponder housing  (refer to arrows in Fig. 2).
Operating mode (only 808613.10)
Following operating modes are eligible for each LED output:
plus switched
 internal resistance Ri = 1 kΩ
minus switched  internal resistance Ri = 1 kΩ
plus switched
 internal resistance Ri = 0 kΩ
minus switched  internal resistance Ri = 0 kΩ
Contact operation
The optocoupler output 1 to 32 may be programmed as plus or
minus controlled with the programming software.
Specification
Loop
Rated voltage
: 8 V DC ... 42 V DC
Rated current
: approx. 50 µA @ 19 V DC
External power supply
Operating voltage
: 10 V DC ... 15 V DC
Quiescent Current
: approx. 3 mA @ 12 V DC
LED outputs
Properties
: 12 V DC / 10 mA
Switching mode
: plus/minus switching
Max. length of
:
max. 100 m (Ri = 1 kΩ)
connection cable
:
max. 3 m (Ri = 0 Ω)
Ambient temperature
: -10 °C ... +50 °C
Storage temperature
: -25 °C ... +75 °C
Rel. humidity
:  95 % rel. humidity
(no condensation)
Protection rating
: IP 40 (with housing)
Weight:
: approx. 95 g
Dimensions (w x h x d)
: 150 x 82 x 20 (mm)
Specification
: EN 54 - 17:2005/-18:2005
VdS Approval
: G 206044
Declaration of Performance
: DoP-20611130701
Additional and updated Information
The product specifications relate to the date of issue and
may differ due to modifications and/or amended
Standards and Regulations from the given information.
For updated information and declaration of conformity
refer to www.esser-systems.com.
Observe technical manuals of the FACP to ensure
compliance to standards and local requirements of
Systems features!
esserbus
®
and essernet
®
are registered trademarks in
Germany.
Refer to the Fire Alarm System Catalogue for additional
accessories.
Programming
software tools 8000
from Version V1.19
from Version V1.20
from Version V1.15
from Version V1.16
from Version V1.15

Werbung

loading

Inhaltszusammenfassung für Honeywell esser 808611.10

  • Seite 1 798848.10 transponder Technical changes reserved! Koppler 05.2015 / AA © 2015 Honeywell International Inc. The DC / DC converter (Part No. 781336) is required for this Zur Anschaltung an diese BMZ ist der Spannungskonverter FACP connection. (Art.-Nr. 781336) erforderlich! System restrictions Systemgrenzen ...
  • Seite 2 Anschlussklemmen der Optokoppler-Ausgänge 1 bis 32 Terminals for optocoupler outputs 1 to 32 X1, X2 (plus- / minusschaltend abhängig von der Kundendatenprogrammierung) (plus / minus switched, relating to the customer data programming) X3, X5 Anschlussklemmen +12 V DC (gleiches Potential wie Anschlussklemme X8/+U Terminals +12 V DC (same potential as terminal X8/+U X4, X6 Anschlussklemmen GND (gleiches Potential wie Anschlussklemme X8/GND)