Herunterladen Diese Seite drucken

DAB Evoplus Small 40/180 M Installationsanweisung Und Wartung Seite 25

V2.0
Vorschau ausblenden Andere Handbücher für Evoplus Small 40/180 M:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 87
Alarms Log
manently in the alarms log (up to a maximum of 15
alarms). For each recorded alarm a page composed
of 3 parts is displayed: an alphanumeric code that
fault in graphic mode, and a message in the language
selected on Page 10.0, giving a brief description of
the fault.
By pressing the right button you can scroll through all
the pages of the log.
2 questions appear at the end of the log:
1."Reset Alarms?"
Pressing OK (left button) resets any alarms still pre-
sent in the system.
2."Delete Alarms Log"
Pressing OK (left button) deletes the alarms memo-
rised in the log.
Page 13.0
On page 13.0 you can set the system status in ON
or OFF.
If ON is selected the pump is always on.
If OFF is selected the pump is always off.
13.
Parameter
Regulating mode
Twin operating mode
Pump start control
Tabella 2: Impostazioni di fabbrica
Value
= Proportional differential pressure
regulation
= Alternate every 24h
ON
14.
-
Alarm Code
Alarm Symbol
e0 - e16; e21
e17 - e19
e20
e22 - e31
e32 - e35
e37
e38
e39 - e40
e46
e42
e56
e57
e58
15. DISPOSAL
This product or any part of it must be disposed of correctly:
1. Use public or private local systems for waste collection.
2. If that is not possible, contact Dab Pumps or the nearest authorised
service workshop.
Alarm Description
Internal Error
Short Circuit
Voltage Error
Internal Error
Electronic system excess temperature
Low voltage
High voltage
Pump blocked
Pump Disconnected
Dry operation
Motor excess temperature (motor
protector trips)
Frequency of PWM external signal less
than 100 Hz
Frequency of PWM external signal
greater than 5 kHz
Table 3: List of alarms
GB
ENGLISH
23

Werbung

loading