For the Installer
GENERAL
UKV 200-300/Kyla has several different areas of use.
Cooling:
For systems with cooling, a buffer tank is required if,
for example, a supply air coil operates with a heat pump
and active/passive cooling.
Volume expansion:
In the context of heat pumps, approx. 20 l/kW is required
and many heating systems do not have such a volume.
To prevent operational problems, the volume is then
expanded using a UKV 200-300/Kyla.
Flow increaser:
If the heating flow can be restricted without control, a
UKV 200-300/Kyla is installed as an intermediate tank.
This ensures a secure flow for the heat pump and allows
a high flow to the heating system.
Eliminating heat spikes:
In some installations, so-called heat spikes occur as a
result of movements during temperature changes. To
eliminate temporary temperature changes, install a
UKV 200-300/Kyla after the heating installation.
The accumulator tank consists of a condensation-insu-
lated steel vessel with Freon-free polyurethane insula-
tion. External cladding made of durable plastic.
The accumulator tank is designed and manufactured for
a maximum cut-off pressure of 6 bar.
The working temperature is -10 to +95 °C.
TRANSPORT
UKV 200-300/Kyla should be transported and stored
vertically in a dry place. The UKV 200-300/Kyla may,
however, be carefully laid on its back when being moved
into a building.
ASSEMBLY
UKV 200-300/Kyla must only be installed vertically.
The accumulator tank must be installed in a dry area at
a temperature that does not drop below 0 °C (frost-free).
Position UKV 200-300/Kyla on a firm base that can take
the weight, preferably on a concrete floor or foundation.
Use the product's adjustable feet to obtain a horizontal
and stable set-up.
UKV 200-300/Kyla | GB
All manuals and user guides at all-guides.com
0
R
0
R
H M flo w 4 9 (5 0 )
H o t w a te r 5 1 °C
°C
+ 2
0
-2
1
R
0
H o t w a te r 5 1 °C
H M flo w 4 9 (5 0 )
°C
+ 2
0
-2
1
R
0
17

Werbung

loading

Diese Anleitung auch für:

Ukv 300/kylaUkv 200 kyla