Herunterladen Diese Seite drucken

ABB FIO-11 Kurzanleitung Seite 4

Analog-e/a-erweiterungsmodul
Vorschau ausblenden Andere Handbücher für FIO-11:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4
3. Push in the locking tab (7).
4. Tighten the grounding screw (2) to a torque of 0.5 N·m (4 lbf·in).
If you need to remove the adapter module after it has been installed into
the drive, use a suitable tool (e.g. small pliers) to carefully pull out the
locking tab. Then loosen the screw and pull out the module.
Note: The screw tightens the connections and grounds the module. It is
essential for fulfilling the EMC requirements and for proper operation of
the module.
Terminal designations
Marking
X71, X72, X73
1
2
X74
1
2
X75, X76
1
2
Wiring
Use max. 2.5 mm
the drive end to a signal ground terminal. Refer to hardware manual of
the drive or unit for more information.
Do not route signal cables parallel to power cables.
Tighten the signal wiring to 0.5 N·m.
Quick guide - FIO-11
Description
Analog input
• Current input -20...20 mA
AIx+
• Voltage input -10...10 V
AIx-
AO1+
Analog output
• Current output: 0...20 mA
AO1-
DIOx
Digital input/output
• 24 V logic levels for input: "0" < 5 V, "1" > 15 V
COM
• Output current 50 mA source, 50 mA sink
2
conductors for the signals. Ground the cable shield at

Werbung

loading