Analog Value Objects
Property
Object_Identifier
Object_Type
Object_Name
Description
Present_Value
Status_Flags
Event_State
Out_Of_Service
Units
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
Instance
Object_Name
default
1
"DriveTime1"
2
"DriveTime2"
3
"DriveTime3"
4
"DriveTime4"
5
"TurnOffTime1"
6
"TurnOffTime2"
7
"TurnOffTime3"
8
"TurnOffTime4"
9
"RcvHrtBt1"
10
"RcvHrtBt2"
11
"RcvHrtBt3"
12
"RcvHrtBt4"
Analog-value 1...12 by default are disabled and not accessible.
They are enabled in operating mode Motorized_Damper with multistate-value 1...4.
PICS_MB-BAC-WA1-4_v1.0.doc
TROXNETCOM Funktionsmodul MB-BAC-WA1/4
Remark / Value
analog-value, instance 1 ... 12
ANALOG_VALUE (2)
max. 42 Bytes
max. 84 Bytes, default ""
0...6553,4
IN_ALARM:
0
FAULT:
0
OVERRIDDEN:
0
OUT_OF_SERVICE:
0
NORMAL (0)
FALSE (0)
seconds (73)
Present_Value
default
240.0
240.0
240.0
240.0
35.0
35.0
35.0
35.0
0.0
0.0
0.0
0.0
- 5 -
RW
R
R
RW-E
RW-E
RW-E
R
R
R
R
31